A Decoupled Approach for Modeling N-k Interdiction with Induced Failures in Electric Power Grids

Andrew Chio, Kaarthik Sundar, Russell Bent, Nalini Venkatasubramanian

eess.SY ·submitted 2026-10-13 23:08 UTC · v1
benchmark

Abstract

The electric power grid is a critical infrastructure system subject to different types of failures which can have devastating impacts on society. One framework to study the resilience of the grid is the N-k interdiction model, which introduces an attacker and defender model to identify grid vulnerabilities. However, traditional N-k interdiction models characterize the power grid with steady-state assumptions. One key aspect missing from this analysis is the behavior of the grid as it evolves from the pre-failure grid state and post-failure grid state. During such a transition period, automated protection systems, transient instabilities, and other phenomena can trigger cascading failures that can occur before grid operators can respond. To bridge this gap, this paper first introduces the generalized induced failure N-k (N-k.k') problem, where an initial set of k failures induces an additional set of k' failures. In this context, we propose a disjoint optimization approach that decouples the computation of cascading failures from the interdiction model. This system response model, furthermore, is treated as a black box module without compromising the underlying performance guarantees of the interdiction model. Extensive experiments on several benchmark power grid case studies showcase the efficacy and scalability of the approach.

Closest papers

Nearest neighbours by meaning across the whole index.

LLM-Guided Cyber-Physical Attack Path Identification in Smart Grids

cs.CR cs.AI ·2026-11-18 ·Amr Elshazly, Jesse Roberts, Rachad Atat, Muhammad Ismail
published similarity 0.65
Abstract · 7 pages, 4 figures, 1 table. Accepted at IEEE IECON 2026

Identifying high-impact attack paths in cyber-physical power systems is critical for improving grid resilience. Existing methods typically rely on either structural topology analysis or simulation-based cascading-failure models. Topology-based approaches capture connectivity but lack adversarial reasoning, while simulation-driven methods are primarily suited for offline analysis and are less effective for rapid evaluation of evolving attack scenarios. As a result, identifying realistic attack paths that jointly capture topology, threat semantics, and physical impact remains challenging. This paper presents a physics-grounded framework for identifying cyber-physical attack paths using large language models (LLMs), with cascading-failure-derived impact rankings used as physics-grounded references. The framework integrates system topology, LLM-guided STRIDE and MITRE ATT&CK threat modeling, and three baseline strategies for comparison: topology-driven, threat-driven, and fusion-based. Evaluation is performed using (i) critical-node overlap between LLM-inferred top-K rankings and cascading-failure-based ground truth; (ii) node-level similarity between LLM-inferred and reference paths; and (iii) path-level alignment capturing agreement in complete attack sequences. Results show that structured LLM-based threat modeling substantially improves alignment with physics-grounded references. In the cyber layer, critical-node overlap@3 increases from approximately 33% to as high as 100%, while node-level similarity reaches up to 65% and path-level alignment reaches up to 48%. In addition, the proposed framework reduces runtime by approximately 75--85% compared to the fusion-based baseline in the IEEE 14-bus system. These results suggest that LLM-guided attack path identification is a promising approach for efficient and impact-aware cyber-physical security analysis.

0.35

GRID-MRI: Resilience Assessment of Power Systems under Coordinated Cyber-Physical Attacks

eess.SY cs.CR ·2026-11-12 ·Isaac Ortega Romero, Ioannis Zografopoulos
similarity 0.64
Abstract · IEEE PESGM 2027, 5 pages

The increasing penetration of inverter-based resources and growing cyber-physical interdependencies expose electrical power systems to disturbances that challenge conventional resilience assessments. Existing approaches often evaluate resilience dimensions independently, overlooking the non-additive effects of coordinated disruptions and the influence of exogenous stressors. To address this gap, this paper proposes a Grid Multidimensional Resilience Index (GRID-MRI) that integrates endogenous disruption severity, coordination effects, and climatic and economic-regulatory conditions. The framework quantifies physical, cyber, and operational degradation, identifies interaction effects through counterfactual (i.e., what-if), simulations of individual and coordinated attacks, and incorporates exogenous stressors as scenario-dependent scaling factors. Its application to a modified IEEE 39-bus system under three escalating cyber-physical attack scenarios, informed by the December 2025 Polish cyberattack incident, reveals that coordinated attacks induce system collapse despite stable individual and additive responses. The corresponding resilience losses are 3.72 and 4.09 times their additive estimates, while GRID-MRI increases from 0.062 to 1.188 and reaches 6.081 under additional exogenous stress. These findings demonstrate the limitations of additive assessments and establish a quantitative basis for distinguishing the dominant mechanisms of multidimensional resilience degradation.

0.28

RESILAGENT: A Three-Pillar Architecture for Cyber-Physical Resilience in Electrical Power and Energy Systems

cs.CR cs.AIeess.SY ·2026-11-16 ·Nikolaos Kekatos, Georgios Koutidis, Konstantinos Antonakopoulos, Stylianos Basagiannis, Sokratis Katsikas +4 more
publishedbenchmark similarity 0.62
Abstract · 7 pages, 5 figures, 1 table. Accepted at the 2026 IEEE International Conference on Cyber Security and Resilience (IEEE CSR 2026)

Electrical Power and Energy Systems face hybrid threats that combine cyber intrusions, physical sabotage and climate-driven stress, and routinely outpace today's siloed monitoring stacks. We present RESILAGENT, a concept architecture organised around three operational pillars, Sensing & Data Intelligence, Resilience Analytics & Reporting, and Incident Response & Recovery, mediated by a Cloud-based Orchestrator and exercised through a closed Detect-Simulate-Decide-Sign loop. The framework fuses agentic artificial intelligence and multimodal large language models for cross-modal detection, real-time digital twins for what-if simulation, and a permissioned blockchain anchor for tamper-evident threat intelligence and CER/NIS2-aligned evidence. We instantiate it on two scenarios, a transmission operator under coordinated cyber compromise, sabotage and heatwave, and a distribution operator under a supply-chain compromise during a storm, and report an IEEE-bus micro-benchmark that quantifies each pillar through false-data-injection attack detection, cyber-physical fusion lift, N-1 contingency screening and anchor cost.

0.42

AIDC Microgrid Vulnerability Assessment Under Computing-Power Coordinated Attacks

eess.SY ·2026-08-11 ·Ze Yu, Hongwei Zhen, Chao Shen, Mingyang Sun
similarity 0.58
Abstract

The rapid growth of large language model (LLM) services is expanding AI data centers (AIDCs), increasing electricity demand and associated carbon emissions. Renewable energy integration can mitigate these impacts but also strengthens the coupling between AIDC loads and inverter-interfaced generation, creating cross-domain cyber-physical vulnerabilities. Specifically, adversarial AI requests alter AIDC power demand, whereas inverter control tampering modifies source-side dynamics, and their combined impact on system stability varies with generation forecast and demand response uncertainties. To this end, we propose an uncertainty-aware AIDC microgrid vulnerability assessment framework under computing-power coordinated attacks. First, the framework maps adversarial AI requests to AIDC power variations and represents uncertainties in attack-induced demand responses and photovoltaic (PV) forecasts through confidence-weighted realizations. Then, impedance based stability analysis combines these realizations with bounded inverter parameter tampering to construct attack reachable domains and identify critical attack time windows. Furthermore, a separate criterion identifies fixed coordinated attack vectors that retain destabilizing capability throughout each selected window. Case studies demonstrate that, unlike either attack component applied alone, coordinated attacks within identified critical windows induce sustained inverter frequency oscillations with peak absolute deviations exceeding 20% of nominal frequency, whereas the evaluated out-of-window response remains bounded. The proposed method further identifies critical attack windows and the associated coordinated attack vectors.

0.04

A Systematic Evaluation of Machine Learning Methods for Fault Detection and Line Identification in Electrical Power Grids

cs.LG eess.SP ·2026-09-15 ·Julian Oelhaf, Georg Kordowich, Paula Andrea Pérez-Toro, Tomás Arias-Vergara, Andreas Maier +2 more
publishedhighly cited similarity 0.58
Abstract · Accepted at ICASSP 2025. 5 pages, 4 figures. Published version: DOI 10.1109/ICASSP49660.2025.10890544

The integration of renewable energy sources into the electrical grid introduces complex challenges in fault detection and coordination of grid recovery mechanisms. Traditional relay protection systems, which operate based on static rules and predefined thresholds, are inadequate for addressing these challenges, particularly in detecting and isolating faults such as short circuits. Consequently, the conventional methodologies applied to electrical network protection frequently fail to achieve optimal performance in fault detection, especially in terms of adherence to safety standards and the selective limitation of damage. Recent research indicates that machine learning (ML)-based approaches can effectively tackle these issues; however, variations in grid configurations and analysis windows have impeded consistent comparative assessments. In this study, we assess the efficacy of various ML models in detecting electrical faults and pinpointing defective transmission lines within a 10 ms measurement interval - a critical time-frame for real-time operational viability, for the first time. The most effective model attained an F1 score of 0.991 +/- 0.018 and demonstrated a processing time of 0.342ms +/- 0.509ms.

0.52

Cascading Contingency Analysis of Modern Power Systems Using a Stochastic Hybrid Systems Framework

eess.SY eess.SP ·2026-11-10 ·Masoud H. Nazari, Hamid Varmazyari
published similarity 0.57
Abstract · This paper was accepted at the 2026 North American Power Symposium (NAPS)

This paper presents a cascading contingency analysis and risk assessment framework that incorporates probabilistic mode transitions motivated by stochastic hybrid system (SHS) concepts together with power-flow-based stress evaluation. A two-stage modeling approach is adopted in which sensitivity-based analysis is first used to identify candidate cascading transitions, followed by DC power flow re-evaluation to accurately capture post-contingency stress redistribution, islanding behavior, and load shedding. A probabilistic propagation model is constructed using mode-dependent transition probabilities derived from line loading conditions. A Cascading Risk Index (CRI) is introduced to quantify the expected load shedding accumulated over cascade progression. Case studies on the IEEE 39-bus system demonstrate that the proposed framework captures diverse cascading routes under multiple initiating outages and identifies critical propagation patterns that are not revealed by N-1/N-2 screening. The results highlight the importance of SHS modeling in assessing cascading risk and providing a scalable framework for resilience evaluation in modern power systems.

0.34

Detecting False Data Injection and Unstable Operation in Smart Grid via System-Aware Graph Boundary Learning

cs.CR ·2026-09-28 ·Emad Efatinasab, Denis Donadel, Mirco Rampazzo, Chuadhry Mujeeb Ahmed
similarity 0.57
Abstract

Cyber-physical power systems increasingly rely on data-driven tools to detect instability and support reliable grid operation. However, reliable stability prediction is difficult when unstable operating configurations are rare, sensitive, or unavailable during model development, since collecting such data safely and at scale is often impractical. At the same time, False Data Injection (FDI) attacks can manipulate reported system parameters to trigger false instability alarms or conceal unsafe operation, and such threats in Decentral Smart Grid Control (DSGC) systems remain largely unexplored. These challenges are rarely addressed jointly, leaving a gap between stability prediction and attack detection that this work aims to close. In this paper, we introduce StarGNN, a graph learning framework that learns the stable operating region exclusively from clean stable configurations and uses a single abnormality score to flag reported configurations that should not be trusted as evidence of safe operation, covering both genuine instability and unseen FDI manipulations. Each configuration is represented as a producer-consumer star graph and processed by a role aware graph neural network, with physics constrained pseudo-negatives generated by perturbing reaction time and price response parameters standing in for the unavailable unstable and attack data. A single threshold, calibrated only on held-out stable data, is used without task or attack specific adjustment. Evaluated on nine unseen FDI scenarios, StarGNN detects between 0.780 and 0.973 of attacks on stable configurations and retains a post attack instability recall between 0.972 and 0.999 on unstable ones, with 0.899 recall against a stronger adaptive attacker, showing that stable-only boundary learning can support both stability prediction and attack detection without access to genuine unstable labels or attack samples during training.

0.13

Robustness of Local Energy Markets to Cyberattacks: Case Study of False Data Injection

cs.CR ·2026-09-29 ·Mehran Moradi, Reza Zamani, Phil Aupke, Andreas Theocharis, Andreas Kassler
similarity 0.56
Abstract

Market clearing in community-based local energy markets relies on power demand and PV forecasts, making it vulnerable to coordinated false data injection (FDI) attacks. This paper proposes a bilevel optimization framework to identify worst-case bus-level FDI against interconnected multi-community electricity markets within a distribution network. The upper level attacker maximizes physical impact, measured by cumulative voltage deviation, while accounting for detectability. The lower level re-clears the interconnected multi-community markets subject to operational and network constraints. The bilevel model is reformulated as a single-level mixed-integer program through Karush-Kuhn-Tucker conditions and solved using the epsilon constraint method to characterize the trade-off between physical impact and detectability. Case studies on the IEEE 33-bus system with three communities show that even bounded, system-level zero-sum attacks can reshape local trading, reduce voltage security margins, and produce asymmetric community-level market outcomes. The results further show that vulnerability depends strongly on the spatiotemporal placement of falsified data rather than on uniform spreading across buses and time periods.

0.26