CS Paper Radar

On the Mechanism of Multi-Cluster System Separation Under Extreme Events

Nikolaos Sofos, Georgios Tzounas, Federico Milano

eess.SY ·submitted 2026-10-14 10:09 UTC · v1
unusual

Abstract

Historical blackout events demonstrate that, under complex multi-event contingencies, interconnected power systems can split into multiple areas exhibiting distinct dynamic behavior while remaining physically connected. This work provides a rationale for this phenomenon. Typical N-1 contingency analysis leads to a response dominated by a single unstable mode, supporting the two-cluster conjecture used by transient stability assessment tools such as the SIME method. However, extreme events, often involving cascading N-k contingencies, can excite multiple unstable modes. We establish a proof of concept based on linear modal expansion to show how such concurrent excitation leads to multiple coherent areas. The resulting behavior is illustrated through simulations on the standard WSCC 9-bus, IEEE 14-bus, and IEEE 39-bus systems, demonstrating the limitations of conventional two-cluster representations under extreme events.

Closest papers

Nearest neighbours by meaning across the whole index.

Cascading Contingency Analysis of Modern Power Systems Using a Stochastic Hybrid Systems Framework

eess.SY eess.SP ·2026-11-10 ·Masoud H. Nazari, Hamid Varmazyari
published similarity 0.55
Abstract · This paper was accepted at the 2026 North American Power Symposium (NAPS)

This paper presents a cascading contingency analysis and risk assessment framework that incorporates probabilistic mode transitions motivated by stochastic hybrid system (SHS) concepts together with power-flow-based stress evaluation. A two-stage modeling approach is adopted in which sensitivity-based analysis is first used to identify candidate cascading transitions, followed by DC power flow re-evaluation to accurately capture post-contingency stress redistribution, islanding behavior, and load shedding. A probabilistic propagation model is constructed using mode-dependent transition probabilities derived from line loading conditions. A Cascading Risk Index (CRI) is introduced to quantify the expected load shedding accumulated over cascade progression. Case studies on the IEEE 39-bus system demonstrate that the proposed framework captures diverse cascading routes under multiple initiating outages and identifies critical propagation patterns that are not revealed by N-1/N-2 screening. The results highlight the importance of SHS modeling in assessing cascading risk and providing a scalable framework for resilience evaluation in modern power systems.

0.34

GRID-MRI: Resilience Assessment of Power Systems under Coordinated Cyber-Physical Attacks

eess.SY cs.CR ·2026-11-12 ·Isaac Ortega Romero, Ioannis Zografopoulos
similarity 0.51
Abstract · IEEE PESGM 2027, 5 pages

The increasing penetration of inverter-based resources and growing cyber-physical interdependencies expose electrical power systems to disturbances that challenge conventional resilience assessments. Existing approaches often evaluate resilience dimensions independently, overlooking the non-additive effects of coordinated disruptions and the influence of exogenous stressors. To address this gap, this paper proposes a Grid Multidimensional Resilience Index (GRID-MRI) that integrates endogenous disruption severity, coordination effects, and climatic and economic-regulatory conditions. The framework quantifies physical, cyber, and operational degradation, identifies interaction effects through counterfactual (i.e., what-if), simulations of individual and coordinated attacks, and incorporates exogenous stressors as scenario-dependent scaling factors. Its application to a modified IEEE 39-bus system under three escalating cyber-physical attack scenarios, informed by the December 2025 Polish cyberattack incident, reveals that coordinated attacks induce system collapse despite stable individual and additive responses. The corresponding resilience losses are 3.72 and 4.09 times their additive estimates, while GRID-MRI increases from 0.062 to 1.188 and reaches 6.081 under additional exogenous stress. These findings demonstrate the limitations of additive assessments and establish a quantitative basis for distinguishing the dominant mechanisms of multidimensional resilience degradation.

0.28

Attack-Resiliency Analytics for Wide-Area Control Systems in Smart Grids

eess.SY ·2026-09-29 ·Mohammad Zakaria Haider, Prabin Mali, Nur Imtiazul Haque, Muhammad Nadeem, Sumit Paudyal +1 more
similarity 0.49
Abstract

Wide-area monitoring, protection, and control (WAMPAC) systems damp inter-area oscillations in large interconnected grids, but their reliance on synchronized PMU measurements carried over wide-area networks exposes them to false data injection (FDI) attacks. This paper presents an attack-resiliency analytics framework that formally models the coupled dynamics of the wide-area damping loop, automatic generation control, and the governor and excitation systems, and formulates the optimal stealthy FDI attack as a mixed-integer linear program (MILP). The anomaly detection model (ADM) enters as a replaceable constraint set: either a static bad-data detection (BDD) rule or a boundary learned from benign operation calibrated to a common false-positive rate. On the IEEE 39 and 118 bus systems, with reference dynamics validated on an OPAL-RT hardware-in-the-loop testbed, the optimal attack with wide-area access attains 3.3 and 8.1 times the benign objective and reaches a 0.5Hz frequency excursion more than twice as fast as an attack confined to automatic generation control. Learned boundaries reduce the attack objective by 15.5 55.0% and prevent over-frequency relay trips in all configurations, with feasible stealthy attacks remaining in every case, and residual risk tracks the width of the learned boundary rather than the detector family.

0.31

Mode-in-Variance Participation Factors under Stochastic Excitation

eess.SY ·2026-11-12 ·Bruno Pinheiro, Liya Huang, Georgios Tzounas
similarity 0.49
Abstract

This paper investigates how the dynamic modes of a power system contribute to the stationary variance of its variables under continuous stochastic excitation. Using a modal decomposition of the covariance matrix, the variance of each state or algebraic variable can be resolved into components associated with individual modal responses and their interactions. These components are shown to correspond to within-mode variance and cross-modal covariance, respectively, and the corresponding normalized contributions are termed mode-in-variance participation factors (PFs). The proposed PFs can be used to identify modes governing the variability of important system quantities such as frequency and voltage, quantify the effect of modal interactions, and reveal control dynamics that can be targeted to reduce their stochastic variability. These capabilities are demonstrated through case studies based on the Kundur two-area and IEEE 39-bus systems.

0.24

When Gigawatts of Computational Load Disappear: Cycle-Space Certificates for Grid Synchronization and Transient Stability

eess.SY math.DSphysics.soc-ph ·2026-09-23 ·Michael Chertkov
similarity 0.49
Abstract · 13 pages, 2 figures

Rapid growth of data centers and artificial-intelligence services is producing computational loads at scales once associated mainly with largest power plants. Recent grid events show that a routine transmission disturbance can cause several gigawatts of data-center demand to disconnect or transfer to backup nearly at once. This article revisits the classical synchronization and transient-stability theory needed to reason about such events. We organize four lines of work---graph-based synchronization conditions, winding-number descriptions of nonlinear power flow, separable convex network optimization, and direct energy methods---into a single cycle-space certificate framework for the lossless fixed-voltage model. The static layer gives an exact strict-cohesion test within a prescribed winding cell and reveals the widely used Dörfler--Chertkov--Bullo test as a quadratic surrogate of the same convex problem. The dynamic layer converts the critical-energy calculation into a finite family of convex boundary problems. Standard MATPOWER benchmarks illustrate both what the stronger static test gains and where it gains nothing: the 118-bus case admits $16.2\%$ more loading than the sufficient screen, while the 39-bus case is bridge-limited and the thresholds coincide. A stylized $2.7$-GW 39-bus event further shows that transient margin can change by about a factor of two depending on where balancing power is supplied, even when every final balanced operating point remains statically feasible. The result is a tutorial synthesis and an extensible deterministic certificate for emerging gigawatt-scale computational-load contingencies.

0.53

Numerical Stability Issues and a Mitigation Method in Switching Events Calculation Considering State Variable Discontinuities for EMT Simulation

eess.SY ·2026-11-08 ·Sheng Lei
similarity 0.48
Abstract · Copyright may be transferred without notice, after which this version may no longer be accessible

Some existing methods for switching events calculation considering state variable discontinuities for EMT simulation can encounter numerical stability issues, either over-stabilizing or destabilizing the studied power systems. This paper documents these issues in detail with a concrete example. The underlying mechanism of the issues are revealed via systematic analysis. A mitigation method for the issues is proposed. The convergence behavior of the method is analyzed. Numerical examples demonstrate the effectiveness of the method. It is observed that the method also helps to improve the accuracy of the simulation results.

0.29

A Decoupled Approach for Modeling N-k Interdiction with Induced Failures in Electric Power Grids

eess.SY ·2026-10-13 ·Andrew Chio, Kaarthik Sundar, Russell Bent, Nalini Venkatasubramanian
benchmark similarity 0.48
Abstract

The electric power grid is a critical infrastructure system subject to different types of failures which can have devastating impacts on society. One framework to study the resilience of the grid is the N-k interdiction model, which introduces an attacker and defender model to identify grid vulnerabilities. However, traditional N-k interdiction models characterize the power grid with steady-state assumptions. One key aspect missing from this analysis is the behavior of the grid as it evolves from the pre-failure grid state and post-failure grid state. During such a transition period, automated protection systems, transient instabilities, and other phenomena can trigger cascading failures that can occur before grid operators can respond. To bridge this gap, this paper first introduces the generalized induced failure N-k (N-k.k') problem, where an initial set of k failures induces an additional set of k' failures. In this context, we propose a disjoint optimization approach that decouples the computation of cascading failures from the interdiction model. This system response model, furthermore, is treated as a black box module without compromising the underlying performance guarantees of the interdiction model. Extensive experiments on several benchmark power grid case studies showcase the efficacy and scalability of the approach.

0.22

A Nested Heterogeneous Multiscale Framework for Power System Dynamic Simulation

eess.SY ·2026-11-07 ·Kaiyang Huang, Min Xiong, Yang Liu, Kai Sun
similarity 0.47
Abstract · This work has been submitted to the IEEE for possible publication. Copyright may be transferred without notice, after which this version may…

Power system dynamics involve multiple timescales, from electromagnetic transients of the network and inverter-based resources to electromechanical oscillations of synchronous generators and quasi-steady-state evolution of the operating point. Simulating these dynamics with a detailed electromagnetic transient model is computationally prohibitive, whereas existing methods reduce the model to focus on a single timescale and lose accuracy when dynamics of different timescales interact. This paper proposes a nested heterogeneous multiscale framework for highly efficient multi-timescale simulation of a power system represented by one unified detailed model. Rather than varying only the integration step, the framework adaptively shifts the simulation resolution among three nested levels so that the dynamics of interest at each stage are always captured, with the slower dynamics estimated on the fly from short detailed simulations at controlled accuracy. Theoretical analysis proves the stability of long steps during quasi-steady-state evolution and quantifies the attainable speedup. On a modified IEEE 39-bus system with frequency regulation and load restoration, the framework accurately reproduces the dynamics of all timescales and runs 15 to 18 times faster than conventional simulation of the detailed model. The accuracy and speedup of the proposed method are further verified on a 390-bus system, demonstrating its scalability to large power systems.

0.31