Hyperscale Data Centers as Wide-Area Damping Actuators for Low-Inertia Power Systems

Mohamed Shamseldein

eess.SY ·submitted 2026-10-24 15:32 UTC · v1
publishedbenchmark

Abstract

Low-inertia power systems need fast damping actuators as synchronous generation is displaced by inverter-based resources. This paper evaluates hyperscale data-center loads controlled through Dynamic Voltage and Frequency Scaling (DVFS) as wide-area damping actuators. A DAE-consistent bus-input matrix is validated against the ANDES reduced state matrix and a finite-difference input check. On the Kundur two-area benchmark, Bus 10 ranks highest among non-generator buses for the 0.647 Hz inter-area mode. A classical washout-plus-lead-lag controller raises damping from 3.43% to approximately 6%. Modern 10-50 ms battery and DVFS actuators require comparable peak modulation for the same small-signal damping target. Compared with a closest same-system data-center-frequency-droop baseline, the wide-area controller offers a clearer advantage: at comparable peak MW, droop reaches 4.76% damping, while reaching 6% requires approximately twice the peak modulation. In the Pade-delay model, damping crosses the open-loop value at 443 ms for the 10 ms DVFS actuator versus 374 ms for the 50 ms BESS case. Reduced-order saturation stress tests show that a 2 MW envelope is non-binding for modal, fault-cleared-equivalent, and line-outage-equivalent disturbances, but can bind under generator-trip-equivalent stress. IEEE 39-bus tests confirm the DAE-based ranking procedure and show that high-residue buses may require more phase compensation than a single lead-lag stage can supply.

Comment
24 pages, 7 figures. Author manuscript of the published journal article
Journal ref
Smart Grids and Sustainable Energy 11, 43 (2026)
DOI
10.1007/s40866-026-00358-5

Closest papers

Nearest neighbours by meaning across the whole index.

Adaptive Grid-Mode-Aware Hybrid Energy Storage Control for AI Data Center Oscillation Mitigation

eess.SY ·2026-11-04 ·Quang Manh Hoang, Sina Mohammadi, Phi Long Nguyen, Wencong Su, Van-Hai Bui
similarity 0.57
Abstract · Manuscript is submitted to PESGM2027

Oscillatory power components in AI data-center demand can produce large frequency deviations when they coincide with vulnerable grid modes. Mode-aware hybrid energy storage systems (HESSs) can selectively suppress these components, but their effectiveness degrades when the grid mode changes while the control target remains fixed. This paper proposes a closed-loop grid-mode-adaptive HESS control framework that integrates measurement-based modal identification with mode-selective control. A sliding-window N4SID estimator identifies the local grid dynamics from grid-side power and frequency measurements, and the resulting natural-frequency estimate is used to retune the modal suppression branch assigned to the supercapacitor. The framework is evaluated under a grid-mode shift from 0.50 to 1.35Hz while maintaining equal physical damping and approximately equal load excitation at both frequencies. Compared with the fixed-target controller, the adaptive method reduces the post-change grid-side modal power component from 8.78 to 2.02MW, corresponding to a 76.94% reduction, and substantially lowers the resulting frequency deviation.

0.21

A Dynamic Model and Stability Analysis of a Grid-Interactive Data Center

eess.SY ·2026-11-18 ·Advith Natarajan, Xinyang Zhou, Guido Cavraro
similarity 0.56
Abstract

The rapid growth of data centers is creating new interactions between computational workload and power-system dynamics, with potentially significant implications for grid stability. We develop a four-dimensional nonlinear dynamical model of a data center campus interconnected with the bulk power system through a modified Single Machine Infinite Bus system. The model couples generator swing dynamics with a fluid-limit model of computational workload backlog and a grid-interactive data center power controller that incorporates both frequency feedback and computational backpressure. This formulation captures the coupled evolution of generator frequency, rotor angle, computational workload, and data center power consumption, providing a framework for studying the stability implications of flexible data center operation.

0.22

Grid-Forming E-STATCOMs for Stable Integration of Large-Scale Data Centers: Modeling and Control

eess.SY ·2026-09-27 ·Prabhat Ranjan Bana, Novan Zakkia, Jean-Philippe Hasler, Christer Danielsson
published similarity 0.56
Abstract · To be published in CIGRE: Grid of the Future Symposium 2026, in Richmond, Virginia, US

The rapid expansion of large-scale AI data centers (AIDC) is introducing new stability challenges, particularly in weak or low-inertia networks characterized by fast, step-like demand variations and strict requirements on voltage and dynamic performance. This paper investigates the use of grid-forming (GFM) Enhanced STATCOMs (E-STATCOMs) to support reliable integration of such facilities. A power-admittance-based linear modelling framework is developed to capture system interactions and is validated through detailed EMT simulations. The results demonstrate that E-STATCOMs provide fast, well-damped responses to abrupt load changes while effectively mitigating low-frequency oscillations and interactions with network resonances. By enabling tunable dynamic behavior via a load balancer, virtual impedance, and coordinated active-reactive power support, the proposed approach allows precise shaping of system response and improved regulation at the point of connection. These features make E-STATCOMs a flexible and scalable solution for integrating large data centers into weak grids and long transmission systems, supported by a design-oriented framework that facilitates parameter selection and performance assessment without extensive reliance on EMT studies to meet grid codes and AIDC interconnection requirements.

0.24

Data Center Oscillation Isolation and Grid Support: Fundamental Limits and Source-Selective Control

eess.SY math.DS ·2026-10-19 ·Cheng Feng
similarity 0.56
Abstract

The grid integration of large data centers poses a growing power-system stability challenge. Rapidly varying computing demand can induce oscillations, while the facilities must provide a prescribed response to grid disturbances. Existing controls address load fluctuations and grid support but do not establish their jointly achievable performance. This paper derives fundamental limits and develops a source-selective controller for simultaneous oscillation isolation and grid support. A coupled closed-loop model gives a condition for distinguishing disturbance sources and reveals a direct isolation-support conflict under grid-import-power feedback alone; additional electrical measurements can remove this pointwise conflict but leave a conditional cross-frequency sensitivity limit. Guided by these limits, we design a local residual-feedback storage controller through convex frequency-domain optimization with stability, isolation, and grid-response constraints across operating points. Tests on a single-generator interconnection and a modified nine-bus network show stronger oscillation isolation than equal-order optimized comparators while meeting the prescribed grid response across operating points.

0.22

Feasibility of Pareto-Improving Damping Control of Forced Oscillations: The Active-Power Case

eess.SY ·2026-11-13 ·Haozong Wang, Yuru Wu, Yan Wen, Qian Liu, Jiahui Yang +3 more
benchmark similarity 0.55
Abstract

Damping control of a forced oscillation may reduce amplitudes at certain locations while increasing them elsewhere. This paper introduces Pareto improvement as a criterion for assessing such control: at least one nodal oscillation amplitude decreases, while none increases across all other nodes. The analysis considers active-power forcing sources and active-power control injections in connected swing networks with positive inertia and damping. Necessary conditions for Pareto improvement feasibility are derived from the normalized nodal responses. It is proven that for every network with a single oscillation source and a single actuator, at least one positive forcing frequency is shown to preclude Pareto improvement, regardless of the amplitude and phase of the control input. A three-node counterexample shows that this limitation does not persist with multiple actuators. PSS/E simulations of a 6-bus benchmark system and a modified IEEE 39-bus system validated the analysis. These findings suggest the value of assessing control effects across the network and further investigating multi-actuator damping control.

0.39

Communication Delay Robust Control of BESS for AI Training Load Smoothing

eess.SY ·2026-09-18 ·Xue Lyu, Wei Du, Sheik Mohammad Mohiuddin, Brett A. Ross
hot direction similarity 0.55
Abstract · 10 pages, 17 figures

AI training loads can exhibit rapid power fluctuations because their power demand differs significantly between computational and communication phases, creating challenging ramp rates at the data center point of common coupling (PCC). Integrating battery energy storage systems (BESS) in data centers is a promising mitigation option. This paper proposes a hybrid BESS control strategy that combines droop-based grid-forming (GFM) control with instantaneous load current-based compensation to suppress high frequency load fluctuations. The GFM control loop regulates the long-term power exchange of the BESS, while the load-following control provides fast compensation for short-term AI workload fluctuations. Communication delay between the load current measurements and the BESS controller is explicitly modeled, and its impact on smoothing performance is analyzed. To mitigate delay-induced degradation, a predictor-based compensation method is incorporated into the BESS control structure. High-fidelity electromagnetic transient simulations are conducted to validate the proposed approach. Results demonstrate effective smoothing of AI training load fluctuations across different grid strength conditions and under time varying communication delays.

0.28

Mitigating Forced Oscillations in Power Systems via Data-Enabled Predictive Control

eess.SY ·2026-08-27 ·Soraya Daabak, Verena Häberle, Gabriela Hug, Gustavo Valverde
similarity 0.54
Abstract

Sustained forced oscillations in power systems, driven by large cyclic loads such as data centers, pose a challenge to conventional power system stabilizers (PSSs), which rely on fixed tuned parameters and limited adaptability. This paper investigates the use of Data-Enabled Predictive Control (DeePC) as a data-driven alternative for damping such oscillations. DeePC constructs control actions directly from measured trajectories without requiring an explicit system model, enabling adaptation to changing operating conditions. We evaluate the performance of DeePC on a multi-machine two-area system subject to forced oscillations and compare it against a conventional PSS. The study examines the impact of different input-output configurations and the role of representative historical data in the Hankel matrix construction. Results show that DeePC can achieve superior damping. However, its effectiveness depends critically on the quality and representativeness of the underlying dataset. These findings highlight the potential of data-driven predictive control to complement or outperform conventional stabilizers in modern power systems with evolving and uncertain dynamics.

0.24

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters

eess.SY ·2026-11-13 ·Ziqi Zhou, Mahdieh S. Sadabadi, Sante Pugliese, Xiaoqiang Li, Xiaojie Wu +1 more
hot direction similarity 0.54
Abstract · This paper has 6 pages with 5 figures. The target journal will be determined at a later stage

Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances. This letter proposes a frequency-response-based method to assess finite-duration inertial support using complex terminal power--frequency responses, such as those provided by Network Frequency Perturbation (NFP) plots. For GFMs with nonzero steady-state droop, a duration-dependent energy-equivalent inertia is defined after subtracting the ideal static-droop contribution. An exact spectral relationship is established, expressing this metric as a duration-weighted integral of frequency-dependent inertia, without requiring knowledge of the internal controller structure and parameters. The duration dependence of the metric is further shown to encode observable oscillation frequencies and damping ratios. A coefficient-decoupling GFM control with identical scalar inertia and droop across different settings is used for verification.

0.34