Feasibility of Pareto-Improving Damping Control of Forced Oscillations: The Active-Power Case

Haozong Wang, Yuru Wu, Yan Wen, Qian Liu, Jiahui Yang, Yayu Yang, Muhammad Umar Afzaal, Yilu Liu

eess.SY ·submitted 2026-11-13 02:12 UTC · v1
benchmark

Abstract

Damping control of a forced oscillation may reduce amplitudes at certain locations while increasing them elsewhere. This paper introduces Pareto improvement as a criterion for assessing such control: at least one nodal oscillation amplitude decreases, while none increases across all other nodes. The analysis considers active-power forcing sources and active-power control injections in connected swing networks with positive inertia and damping. Necessary conditions for Pareto improvement feasibility are derived from the normalized nodal responses. It is proven that for every network with a single oscillation source and a single actuator, at least one positive forcing frequency is shown to preclude Pareto improvement, regardless of the amplitude and phase of the control input. A three-node counterexample shows that this limitation does not persist with multiple actuators. PSS/E simulations of a 6-bus benchmark system and a modified IEEE 39-bus system validated the analysis. These findings suggest the value of assessing control effects across the network and further investigating multi-actuator damping control.

Closest papers

Nearest neighbours by meaning across the whole index.

Latent resonances in oscillator networks

eess.SY nlin.AOphysics.soc-ph ·2026-11-13 ·Junjie Xiao, Renaud Lambiotte, Hiroshi Kori
theory similarity 0.56
Abstract · 22 pages, 5 figures, Supplementary Materials included (6 figures, 7 tables)

In networks of coupled oscillators, from neural circuits to power grids, damping is expected to suppress oscillations because of its dissipativity. Here we show that local damping can, counterintuitively, amplify oscillations along some input-output channels, while the network's global oscillation energy decreases and its spectral properties improve. The amplified oscillation arises from a latent resonance that lies in the spectrum yet barely manifests. The added passive damping reshapes this resonance by mixing it with adjacent eigenmodes. In random power-grid networks, damping can boost weakly responding channels by more than an order of magnitude, while subdominant channels can grow to exceed the originally strongest channel. Damping thus not only suppresses oscillations but also provides a way to redistribute oscillatory energy. For any passive network, the amplified response and its upper bound follow exactly from baseline quantities, offering a principled route for network design and control.

0.33

Hyperscale Data Centers as Wide-Area Damping Actuators for Low-Inertia Power Systems

eess.SY ·2026-10-24 ·Mohamed Shamseldein
publishedbenchmark similarity 0.55
Abstract · 24 pages, 7 figures. Author manuscript of the published journal article

Low-inertia power systems need fast damping actuators as synchronous generation is displaced by inverter-based resources. This paper evaluates hyperscale data-center loads controlled through Dynamic Voltage and Frequency Scaling (DVFS) as wide-area damping actuators. A DAE-consistent bus-input matrix is validated against the ANDES reduced state matrix and a finite-difference input check. On the Kundur two-area benchmark, Bus 10 ranks highest among non-generator buses for the 0.647 Hz inter-area mode. A classical washout-plus-lead-lag controller raises damping from 3.43% to approximately 6%. Modern 10-50 ms battery and DVFS actuators require comparable peak modulation for the same small-signal damping target. Compared with a closest same-system data-center-frequency-droop baseline, the wide-area controller offers a clearer advantage: at comparable peak MW, droop reaches 4.76% damping, while reaching 6% requires approximately twice the peak modulation. In the Pade-delay model, damping crosses the open-loop value at 443 ms for the 10 ms DVFS actuator versus 374 ms for the 50 ms BESS case. Reduced-order saturation stress tests show that a 2 MW envelope is non-binding for modal, fault-cleared-equivalent, and line-outage-equivalent disturbances, but can bind under generator-trip-equivalent stress. IEEE 39-bus tests confirm the DAE-based ranking procedure and show that high-residue buses may require more phase compensation than a single lead-lag stage can supply.

0.37

Reduced-Order Model Characterization of Nonlinear Sustained Oscillations

eess.SY math.DS ·2026-09-27 ·Kaiyang Huang, Dan Wilson, Kai Sun
similarity 0.52
Abstract

Nonlinear sustained oscillations involving inverter-based resources can happen when device and network interactions produce an attracting limit cycle around an unstable equilibrium. A damping controller must then describe nonlinear dynamics over the region between the two invariant sets, where a local equilibrium linearization can be insufficient. In this paper, a controlled phase--isostable model is first developed on a two-dimensional invariant manifold connecting the equilibrium and the limit cycle. Dynamics on this surface are represented by phase and isostable coordinates, while physical states and control inputs are related to these coordinates through nonlinear reconstruction and response functions. The required functions are computed from connecting trajectories and periodic-orbit data. A control strategy is then designed to provide extra damping while limiting phase distortion. Case studies on a two-area system and an IEEE 39-bus system demonstrate more effective oscillation damping than the compared equilibrium-linearized designs under the same conditions.

0.27

Forced Oscillations in Power Systems Induced by Data Centers Hosting AI Workloads

eess.SY ·2026-09-23 ·Jovan Krajacic, Georgia Pierrou, Maitraya Desai, Gabriela Hug, Gustavo Valverde
similarity 0.52
Abstract · Revised and extended version of the manuscript previously posted on TechRxiv: https://www.techrxiv.org/doi/full/10.36227/techrxiv.176127304.…

Power swings in large Data Centers (DTCs) running Artificial Intelligence (AI) workloads can excite poorly damped modes in power systems. The resulting forced oscillations can lead to flicker, equipment disconnection, or blackouts. This paper investigates the risks of such load fluctuations for different system strengths and damping conditions. Using an analytical approach based on transfer functions, we identify critical DTC locations in the power grid at which load fluctuations could induce the largest forced oscillations and further characterize the harmonic spectrum of the resulting system response. Depending on the frequency and magnitude of the DTC load fluctuations, forced oscillations can become unbounded. The underlying instabilities are classified into saddle-node bifurcations of the forced periodic response and impasse-surface encounters, using Floquet multipliers and the minimum singular value of the algebraic Jacobian. Furthermore, the impact of different duty cycles and harmonic components beyond the fundamental oscillation frequency in square-wave load profiles is analyzed. Finally, the interaction of two oscillating DTCs is investigated for different locations and forcing frequencies, considering both synchronized and unsynchronized operation. The findings can help system operators to define new regulations on the maximum load fluctuations permitted for DTC facilities at specific grid locations, without negatively affecting the stability and operation of the system.

0.56

Guidelines for the implementation of power oscillation damping controllers in power converters

eess.SY ·2026-09-02 ·Javier Renedo, Macarena Martín Almenta, Sergio Martínez Villanueva, Agustín Díaz-García, Antonio Cordón +1 more
similarity 0.50
Abstract

One of the most effective ways to damp electromechanical oscillations in power systems is by means of supplementary controllers attached to the different devices in the power system is by means of power system stabilizers (PSS) in synchronous machines or by means of power oscillation damping (POD) controllers in facilities with power converters. In the recent years, the use of POD controllers in voltage source converters (VSCs) with grid-following (GFL) control has been investigated. Although the potential of POD controllers to help to damp inter-area oscillations in power systems is enormous, their correct implementation is not trivial, because their effectiveness is strongly linked to their settings. This paper provides guidelines for the implementation of POD controllers in power converters for application in real-world power systems. The paper proposes compliance criteria for POD controllers using a synthetic test system and a systematic methodology used in Spanish technical standard for monitoring compliance (NTS), considering practical considerations. The paper also includes numerical examples to illustrate compliance criteria for POD controllers in a synthetic test system. A generic power converter with grid-following (GFL) control is used for the analysis by simulation and POD controllers using modulation of active-power injection (POD-P), reactive-power injection (POD-Q) or both simultaneously (POD-PQ) will be analysed. Results were validated in a large-scale power system. The paper concludes that by using appropriate synthetic systems, methodologies and compliance criteria, POD controllers in power converters could be effective to damp electromechanical oscillation in large-scale power systems.

0.33

Mitigating Forced Oscillations in Power Systems via Data-Enabled Predictive Control

eess.SY ·2026-08-27 ·Soraya Daabak, Verena Häberle, Gabriela Hug, Gustavo Valverde
similarity 0.49
Abstract

Sustained forced oscillations in power systems, driven by large cyclic loads such as data centers, pose a challenge to conventional power system stabilizers (PSSs), which rely on fixed tuned parameters and limited adaptability. This paper investigates the use of Data-Enabled Predictive Control (DeePC) as a data-driven alternative for damping such oscillations. DeePC constructs control actions directly from measured trajectories without requiring an explicit system model, enabling adaptation to changing operating conditions. We evaluate the performance of DeePC on a multi-machine two-area system subject to forced oscillations and compare it against a conventional PSS. The study examines the impact of different input-output configurations and the role of representative historical data in the Hankel matrix construction. Results show that DeePC can achieve superior damping. However, its effectiveness depends critically on the quality and representativeness of the underlying dataset. These findings highlight the potential of data-driven predictive control to complement or outperform conventional stabilizers in modern power systems with evolving and uncertain dynamics.

0.24

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters

eess.SY ·2026-11-13 ·Ziqi Zhou, Mahdieh S. Sadabadi, Sante Pugliese, Xiaoqiang Li, Xiaojie Wu +1 more
hot direction similarity 0.48
Abstract · This paper has 6 pages with 5 figures. The target journal will be determined at a later stage

Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances. This letter proposes a frequency-response-based method to assess finite-duration inertial support using complex terminal power--frequency responses, such as those provided by Network Frequency Perturbation (NFP) plots. For GFMs with nonzero steady-state droop, a duration-dependent energy-equivalent inertia is defined after subtracting the ideal static-droop contribution. An exact spectral relationship is established, expressing this metric as a duration-weighted integral of frequency-dependent inertia, without requiring knowledge of the internal controller structure and parameters. The duration dependence of the metric is further shown to encode observable oscillation frequencies and damping ratios. A coefficient-decoupling GFM control with identical scalar inertia and droop across different settings is used for verification.

0.27

Conflict-Aware Impedance-Sensitivity-Based Tuning for Multi-Mode Damping Enhancement

eess.SY ·2026-11-04 ·Quang Manh Hoang, Xuan Thanh Trinh, Sina Zarrabian, Akhtar Hussain, Van-Hai Bui
similarity 0.48
Abstract · Manuscript is submitted to PESGM2027

Impedance-based eigenvalue sensitivity provides a practical way to relate converter parameters to poorly damped system modes, but tuning becomes nontrivial when one parameter improves one target mode while degrading another. This paper introduces a conflict-aware tuning strategy for simultaneous damping enhancement of multiple modes. The method converts impedance-derived eigenvalue sensitivities into normalized damping-ratio sensitivities, diagnoses opposing modal tuning directions, and selects either one parameter or a coordinated pair at each iteration. A low-dimensional max--min problem maximizes the predicted damping of the worst target mode subject to parameter limits, protected-mode constraints, and implementation-specific feasibility requirements. Each accepted update is verified on the full system model and the sensitivities are recomputed. Studies on a four-bus system and a modified IEEE 14-bus system demonstrate the value of pairwise coordination, including a case in which single-parameter tuning stops before the predefined damping target is reached.