AGI: Agility Index for Power Systems Dynamic Performance, Inspired by Reynolds Number

Maria Vabson, Amir Sajadi, Bri-Mathias Hodge

eess.SY ·submitted 2026-11-13 22:33 UTC · v1

Abstract

Multiple established metrics and indices exist to quantify the dynamic performance of power systems. With the growth of inverter based resources, these mostly conventional metrics and indices may not encompass all important elements and variables that hold information about the grid performance, especially the damping properties. This paper proposes the Agility Index (AGI), which is a Reynolds number-inspired metric for power system dynamics relating the ratio of inertia to damping. With the current trends towards high-power inverter assets and reduced-inertia grids, explicit attention is necessary in monitoring inertia and damping together. This paper shares insights the AGI presents about the dynamic performance of power systems.

Closest papers

Nearest neighbours by meaning across the whole index.

Frequency Measurement Practices for Inertia Assessment in Inverter Based Resources Dominated Power Systems

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.61
Abstract · Under Review in IEEE Transactions on Power Systems

Transmission system operators and protective relays compute the rate of change of frequency (RoCoF) from frequency averaged over tens to hundreds of milliseconds, as standards and grid codes specify. Any response delivered inside that window lowers the measured RoCoF, so the inferred inertia depends on the window and the responses in service. This paper defines the windowed inertia estimate and derives an exact identity the system inertia divided by one minus the fraction of the disturbance energy delivered inside the window and a closed-form prediction that applies the same estimator to the trajectory of a linear response model. Eleven IEEE 9-bus RMS runs synchronous, grid-following and grid-forming configurations, disturbance sizes and parameter sweeps are reproduced by that model, and the identity closes on the measured response powers. Fast frequency response inflates the estimate most: at 500 ms a grid-following system with 20 % less synchronous inertia reports the same value as the all-synchronous system, the grid-forming system a higher one. On a reduced Greek transmission system the 500ms estimate exceeds the inertia by 17-26%, and a scenario with 10% less synchronous inertia reports more than the all-synchronous scenario's inertia. Operators can thus compute what their measurement reports.

0.26

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters

eess.SY ·2026-11-13 ·Ziqi Zhou, Mahdieh S. Sadabadi, Sante Pugliese, Xiaoqiang Li, Xiaojie Wu +1 more
hot direction similarity 0.57
Abstract · This paper has 6 pages with 5 figures. The target journal will be determined at a later stage

Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances. This letter proposes a frequency-response-based method to assess finite-duration inertial support using complex terminal power--frequency responses, such as those provided by Network Frequency Perturbation (NFP) plots. For GFMs with nonzero steady-state droop, a duration-dependent energy-equivalent inertia is defined after subtracting the ideal static-droop contribution. An exact spectral relationship is established, expressing this metric as a duration-weighted integral of frequency-dependent inertia, without requiring knowledge of the internal controller structure and parameters. The duration dependence of the metric is further shown to encode observable oscillation frequencies and damping ratios. A coefficient-decoupling GFM control with identical scalar inertia and droop across different settings is used for verification.

0.27

Evaluating Grid Strength with Rising Penetration of Inverter Based Resources

eess.SY ·2026-09-22 ·Mohammed N. Khamees, Gad Ilunga, Zhongxia Zhang, Richard E. Tuck
published similarity 0.55
Abstract · Accepted for publication in 2026 CIGRE USNC Grid of the Future (GOTF) Symposium

Over the years, Dominion Energy Virginia (DEV) has experienced recurring power quality disturbances, including voltage and power oscillations, particularly in areas with significant inverter-based generation. While these phenomena suggest a potential relationship to system strength, no definitive correlation has yet been established. This paper presents methodologies for assessing system strength across the DEV network and identifying regions that may be vulnerable to such disturbances. To this end, three grid-strength metrics are evaluated: the Simple Short-Circuit Ratio (SSCR), the Weighted Short-Circuit Ratio (WSCR), and the Composite Short-Circuit Ratio (CSCR). Historical event data will be analyzed using steady-state snapshots from DEV's proprietary Analysis on Demand (ANODE) platform, which provides 10-minute interval load-flow data. These snapshots will be processed using a developed software tool to compute system strength metrics. The analysis will investigate potential correlations between system strength and observed disturbances. Where such correlations are identified, the study will further evaluate the impact of deploying synchronous condensers (SynCons) as a mitigation strategy.

0.31

Quantifying Grid-Forming Requirements for System Strength: How Much and Where?

eess.SY ·2026-10-06 ·Ambuj Gupta, Balarko Chaudhuri, Mark O'Malley
similarity 0.52
Abstract · 25th Wind & Solar Integration Workshop, Porto, Portugal, 29 September - 02 October 2026

As power systems transition toward inverter-based resource (IBR)-dominated grids, Grid-ForMing (GFM) IBRs are increasingly expected to provide the voltage-source characteristics required to maintain adequate system strength. However, how many GFM IBRs are required, and where they should be located in the grid, remains unclear. This paper investigates the impact of the number and location of GFM IBRs on small-signal system strength. The Jacobian Voltage Stiffness Metric (JVSM), which quantifies the voltage-magnitude and voltage-phase stiffness from frequency-domain Jacobian characteristics, is used as a system-strength measure. The analysis demonstrates that increasing the number of GFM IBRs generally improves system strength; however, configurations with the same number of GFM IBRs can exhibit significantly different bus-wise system-strength characteristics depending on their locations. Thus, this paper provides a quantitative basis for specifying GFM requirements in terms of the resulting system strength, rather than solely in terms of penetration level or the number of GFM IBRs. Case studies on a modified IEEE 39-bus system demonstrate how JVSM can be used to quantify and compare the system-strength impact of different numbers and locations of GFM IBRs, with the resulting strength assessments validated against small-signal oscillatory stability.

0.20

Ranking the Parameters Shaping Grid Dynamics

eess.SY ·2026-10-31 ·Ahmad F. Taha
benchmark similarity 0.52
Abstract

Generator and transmission line parameters do not shape the time-domain behavior of a power system equally; a parameter that dominates one dynamic property can be almost invisible to another. This paper studies how the physical parameters of a detailed and general nonlinear differential algebraic equation (DAE) grid model shape the properties that decide whether system states such as frequencies, voltages, and angles can be inferred, observed, controlled, and kept stable. The rankings are conditional as they depend on where grid sensors and actuators sit, on the operating region and the disturbance, on the network topology, and on other settings that the operator chooses. The framework combines DAE trajectory sensitivities, variational Gramians, and stability margin sensitivities to measure how much each parameter reshapes the network dynamics. On three benchmark systems, the rankings show where dynamic leverage concentrates and where the control-theoretic metrics disagree, and they point to how parameter studies can guide calibration, sensor and actuator placement, and security assessment. The proposed methods herein are also scalable and can be tested on grids with tens of thousands of buses.

0.36

On the Achievable Inertia Constant of Inverter Based Resources

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.52
Abstract · Under Review in IEEE Transactions on Power Systems

As inverter-based resources (IBRs) displace synchronous generators, the inertia they can actually contribute to the grid becomes a critical planning parameter. Unlike synchronous machines, this contribution is bounded simultaneously by the available energy reserve, the converter power rating combined with voltage ride-through (VRT) obligations, and the inertia-emulation control scheme with its activation delay. This paper derives each bound in closed form and combines them into a unified envelope $\Heff(t,λ,V_g)=\min(\HE,\HP,\HC)$, which uses parameters accessible to the system operator to quantify how much inertia a plant can provide at a given loading $λ$, grid voltage $V_g$, and time $t$ after a disturbance. The analysis shows that below a loading-dependent critical voltage, VRT reactive-current priority does not leave active-current headroom for inertial power injection; that the converter overload ratio $κ$ matters mainly during voltage dips; and that de-loading yields a linear, quantifiable inertia gain, while collocated energy storage (ESS) removes the source-coupling constraint, making grid-following (GFL) and grid-forming (GFM) plants with storage equivalent post-activation, up to the GFL activation-delay discount within short RoCoF measurement windows. Simulations on the IEEE 9-bus system confirm the framework and motivate a two-dimensional inertia capability curve $H(λ,V_{g,\min})$ as a grid-code instrument analogous to the P--Q diagram of synchronous generators.

0.28

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.50
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Relative-Degree Wall Restricts Passivity-Based Stability Analysis in Inverter-Dominant Grids

eess.SY ·2026-08-30 ·Xiaoyu Peng, Zhongze Li, Xi Ru, Xinghua Chen, Feng Liu
top venue similarity 0.50
Abstract

This letter reveals a fundamental limitation of passivity-based distributed stability analysis in power systems. Under the standard formulation, passivity certification inherently imposes a relative-degree compatibility constraint that excludes many high-fidelity inverter dynamic models (e.g., those that include electromagnetic transients). Potential extensions of passivity frameworks are discussed to break this limitation.

0.43