Why Three Phases? A Historical and Engineering Reassessment of Phase Order in AC Power Transmission

Kai Sun

eess.SY ·submitted 2026-08-27 16:24 UTC · v1
unusual

Abstract

Three-phase alternating current is so deeply embedded in modern electric-power infrastructure that its phase order is often treated as self-evident. Historically, however, 1-phase and true 2-phase systems were commercially important, while commercial 6-phase transmission was later demonstrated. This paper reassesses why 3 phases became the dominant architecture for bulk AC transmission. A general balanced \(m\)-phase formulation is used to show that constant aggregate instantaneous power is not unique to 3 phases: an ideal balanced 2-phase system also cancels the double-frequency power term and can generate a constant-magnitude rotating field. Consequently, the historical displacement of 2 phases cannot be explained by power smoothness alone. The comparison is instead organized around conductor architecture, insulation stress, machine and transformer utilization, conversion requirements, right-of-way utilization, and technological path dependence. A historical, commercial 6-phase demonstration showed that high-phase-order transmission was technically feasible and could improve corridor utilization. The paper then asks: if PE conversion and protection make phase count less costly, could \(m>3\) offer intrinsic advantages? Six such advantages are identified: modular decomposition into interleaved 3-phase groups, redundant control degrees of freedom, structured modal/fault analysis, increased corridor power density under field constraints, potentially higher natural loading and loadability, and enhanced harmonic/field cancellation. A companion derivation shows that phase count alone does not intrinsically reduce \(I^2R\) loss at fixed total conductor material and phase voltage. As a conditional conclusion, 3 phases are an unusually favorable historical optimum for electromechanical grids, but not a mathematically universal optimum for a future converter-dominated grid.

Closest papers

Nearest neighbours by meaning across the whole index.

An Optimal Power-Flow Grouping Topology for Single-Isolation-Stage Multi-Output Solid-State Transformers

eess.SY ·2026-11-06 ·Yi Hao, Krzysztof Puczko, Levy Ferreira Costa, Liangcai Shu, Dongsheng Yang
similarity 0.51
Abstract · 13 pages, 19 figures. Submitted to IEEE for possible publication

Electric-vehicle dc fast-charging stations and data centers require multiple high-power dc outputs with independently varying demands. Conventional multi-output solid-state transformers typically establish a common dc bus and use downstream dc/dc converters for port-level regulation and, where required, galvanic isolation. A single-isolation-stage solid-state transformer can eliminate this additional high-power interface stage by directly forming multiple isolated outputs from its submodule dc/dc stages. However, because one submodule is generally insufficient for an individual output port, multiple submodules must be connected in parallel, while inter-submodule balancing circuits redistribute power under unbalanced loading. The submodule grouping therefore determines the internal balancing-power paths. Sequential grouping can create long transfer paths and accumulated balancing power, increasing current stress and losses. This paper proposes an optimal power-flow grouping topology that interleaves submodules assigned to different output ports, thereby localizing power redistribution and reducing the power processed by the balancing circuits. Analytical models quantify the required balancing power and its reduction relative to sequential grouping. A coordinated submodule-bypass strategy is also developed, and the remaining output-power capability under different fault scenarios is evaluated. A six-submodule prototype validates the proposed topology. Under the same highly unbalanced operating conditions, the proposed topology reduces the maximum submodule dc-link voltage difference by 63\% and the peak balancing current by 14.5%, while improving the measured efficiency by approximately 5.6% at rated power. Stable post-fault operation is also experimentally demonstrated.

0.40

Equivalent DQ Sequence-Domain Model of Unbalanced Three-Phase Passive Elements for Power Converter Controllers

eess.SY ·2026-09-01 ·Air\án Franc\és, Luis Saz, Rafael Castillo, Dionisio Ramirez, Javier Uceda
publishedtheory similarity 0.50
Abstract · 8 pages, 7 figures, 2023 IEEE Applied Power Electronics Conference and Exposition (APEC)

Equivalent dq0 models of three-phase passive impedances are widely used for the design of three-phase inverter and rectifier controllers in the synchronous frame. However, these equivalent models assume that the impedance in each phase are the same, which is not always applicable. The fact that the impedance in each phase is different, generates second order harmonic content in the dq0 components, which hinders the advantages of the dq0 transformation. To avoid the second harmonic in these scenarios, it is possible to use the Fortescue's theorem to represent any asymmetrical set of three-phase signals as a linear combination of three symmetrical sequences. In the literature, only a few works have attempted to derive the equivalent model of unbalanced three-phase passive elements in the sequence domain, and none is able to account for the interaction between the zero sequence and the positive and negative sequences. This work presents the derivation of the equivalent dq sequence-domain model of unbalanced three-phase passive elements both analytically and with an intuitive graphical approach. Experimental results are shown to validate the proposed models.

0.72

Embedding Single-Phase Grid-Forming Inverters in Three-Phase Unbalanced Power Flow

cs.ET ·2026-09-02 ·Kamini Shahare, Fei Feng, Peng Zhang
similarity 0.49
Abstract

This letter introduces Grid-Forming Three-Phase Power Flow (GFM-3PF), an augmented Newton power flow framework for modeling single-phase grid-forming inverters (GFMs) in three-phase unbalanced networks. The contributions of this work are threefold: 1) developing a two-stage solution strategy based on positive-sequence initialization followed by three-phase phase-domain lifting for robust large-scale computation; 2) incorporating phase-domain unbalanced network modeling with controlled mutual coupling together with phase-dependent, frequency-sensitive load representation; and 3) embedding a single-phase GFM bus model directly into the three-phase unbalanced Newton power flow equations through a common droop-governed frequency state. GFM-3PF is validated on 3-bus, 33-bus, and 118-bus test systems, demonstrating its accuracy, robustness, and scalability.

0.54

Control of Isolated Four-Quadrant Single-Stage Three-/Single-Phase X-Rectifier for EV On-Board Chargers

eess.SY ·2026-10-20 ·Sven Weihe, Jonas Huber
similarity 0.48
Abstract · Submitted to an IEEE journal

The single-stage isolated eXtended-functionality rectifier (X-Rectifier) electric vehicle (EV) on-board charger (OBC) employs 650V GaN monolithic bidirectional power transistors (M-BDS) in the input stage, provides sinusoidal input currents and four-quadrant operation in three-phase and split/single phase grids without power derating, operates from asymmetrical three-phase mains, provides reactive power if needed, and supports extremely asymmetric phase loading in standalone vehicle-to-load (V2L) mode. This paper presents a new improved phase-modular control method for the X-Rectifier that enables tracking of arbitrary and independent phase current references regardless of the instantaneous grid voltage (i.e., enables four-quadrant operation). The method supports grid-tied (i.e., grid-to-vehicle, G2V, or vehicle-to grid, V2G) and grid-forming (i.e., V2L) operation. Further, aiming towards a practical realization of the X-Rectifier, the paper addresses implementation aspects of the M-BDS half-bridges, like commutation logic around the grid-voltage zero crossing, fault handling, and soft-switching behaviour. Finally, a realized 5.5 kVA hardware demonstrator of the X-Rectifier is used to validate the proposed control method experimentally for all operating modes, including grid-tied three- and single-phase four-quadrant operation (G2V, V2G, and full reactive power modes). Further, robust V2L operation is verified with real-world loads, i.e., in three-phase mode with asymmetrical loading of the phases including a woodworking power tool, and in single-phase mode with a high-power vacuum cleaner with high inrush current and hence momentary overload of the X-Rectifier demonstrator.

0.21

Ancillary Services in High-Renewable Power Systems: Comparing Market Design, Emerging Trends, and Future Challenges

eess.SY ·2026-09-29 ·Andreas Makrides, Andrey Churkin, Fei Teng, Pierre Pinson
similarity 0.48
Abstract

Rapid growth in renewable generation is changing power-system operation and increasing the importance of ancillary services for security and reliability. As inverter-based resources displace conventional synchronous generation, system operators must procure a broader set of services spanning five categories: frequency control and reserves, voltage and reactive power support, system stability, restoration, and congestion management. This paper compares ancillary-service market design in Great Britain, Germany, Denmark, Italy, California, Texas, and Australia. It examines how these systems define, procure, remunerate, and coordinate services as variable renewable generation increases. The review develops a consistent product-level classification, provides comparable timing visualisations of frequency-control and reserve products, and maps implementation modalities across services and systems. Four trends emerge: faster and more granular frequency-response products, more explicit procurement of stability capabilities including inertia, system strength, and dynamic voltage support, broader participation by storage, demand-side resources, and other inverter-based resources, and greater use of locational, targeted, and technology-neutral procurement. Challenges include limited harmonisation, incomplete valuation of flexibility and stability capabilities whose value depends on location and operating conditions, barriers to participation by distributed and emerging resources, and insufficient coordination between market and operational arrangements. The comparison finds no convergence towards a single market design and supports differentiated but coordinated ancillary-service frameworks reflecting each service's technical, temporal, and locational characteristics.

0.22

Quantifying Grid-Forming Requirements for System Strength: How Much and Where?

eess.SY ·2026-10-06 ·Ambuj Gupta, Balarko Chaudhuri, Mark O'Malley
similarity 0.47
Abstract · 25th Wind & Solar Integration Workshop, Porto, Portugal, 29 September - 02 October 2026

As power systems transition toward inverter-based resource (IBR)-dominated grids, Grid-ForMing (GFM) IBRs are increasingly expected to provide the voltage-source characteristics required to maintain adequate system strength. However, how many GFM IBRs are required, and where they should be located in the grid, remains unclear. This paper investigates the impact of the number and location of GFM IBRs on small-signal system strength. The Jacobian Voltage Stiffness Metric (JVSM), which quantifies the voltage-magnitude and voltage-phase stiffness from frequency-domain Jacobian characteristics, is used as a system-strength measure. The analysis demonstrates that increasing the number of GFM IBRs generally improves system strength; however, configurations with the same number of GFM IBRs can exhibit significantly different bus-wise system-strength characteristics depending on their locations. Thus, this paper provides a quantitative basis for specifying GFM requirements in terms of the resulting system strength, rather than solely in terms of penetration level or the number of GFM IBRs. Case studies on a modified IEEE 39-bus system demonstrate how JVSM can be used to quantify and compare the system-strength impact of different numbers and locations of GFM IBRs, with the resulting strength assessments validated against small-signal oscillatory stability.

0.20

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.47
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

EPIGRIDS: Documentation and Validation of Seven Open Synthetic Transmission Grid Cases

eess.SY math.OC ·2026-11-13 ·Jonathan M. Snodgrass, Scott Greene, Thomas J. Overbye, Christopher L. DeMarco, Bernard C. Lesieutre
benchmark similarity 0.46
Abstract · 10 pages, 2 figures, 6 tables. Submitted to the IEEE Open Access Journal of Power and Energy. Cases: https://doi.org/10.5281/zenodo.23814538…

This paper documents and checks EPIGRIDS, seven open synthetic transmission grid cases from four independently built networks, made with an optimization-based construction method instead of the graph-statistics method behind most large public synthetic grids. The cases range from 250 to 78,484 buses, with geolocated substations, voltages up to 765 kV, and line parameters taken from conductor data. Each ships under an open license in three common power flow formats that agree at the solved operating point, and the six larger cases have a companion hourly, bus-level load series for one year. The Texas, Florida, and Michigan, Ohio, and Indiana cases are sub-networks of the Eastern case. Every case solves an alternating-current power flow from its stored operating point. With parallel circuits merged, the Eastern and Western cases are 9 and 16% denser than the real interconnections, while graph-statistics cases on the same footprints lie within 6% and meet more published realism criteria. A full single-outage contingency analysis completes on every case, and in an optimal power flow benchmark every case except the New England base case and one of its 12 operating points solves in polar form.

0.31