An Open Synthetic Test System for the Jordanian Transmission Grid

Muhy Eddin Zater, Bri-Mathias Hodge

eess.SY ·submitted 2026-08-31 21:18 UTC · v1
benchmark

Abstract

Open synthetic test systems are essential for reproducible power system research, yet the available cases represent almost exclusively North American and European grids. No open transmission test system exists for any Middle Eastern country, whose grids raise different questions such as single corridor fuel-supply resilience and high-renewable operation within small synchronous systems, and established benchmarks cannot demonstrate. This paper presents a synthetic test system for the Jordanian transmission grid, assembled entirely from public sources, where the real topology is reconstructed from a published diagram and restored to its 2018 energized state, with plant-level generation and renewable fleets, per-site hourly profiles, and loads calibrated to the values published by Jordan's grid operators. The case is validated through structural statistics against real-grid criteria, power flow and $N\!-\!1$ screening, an energy-weighted loss decomposition, in addition to a full-year production-cost run compared against the published per-plant energy, and cross-solver verification. The model reproduces the annual energy mix at technology level (largest producers within 4\%, system total within 0.1\%), and the released dataset includes the bus-identity key, all scripts, and a post-2019 scenario variant. This test case is designed to benchmark system-level resource adequacy, time-series dispatch and unit commitment, renewable integration, fuel-supply resilience scenarios, interconnection studies and steady-state studies.

Closest papers

Nearest neighbours by meaning across the whole index.

EPIGRIDS: Documentation and Validation of Seven Open Synthetic Transmission Grid Cases

eess.SY math.OC ·2026-11-13 ·Jonathan M. Snodgrass, Scott Greene, Thomas J. Overbye, Christopher L. DeMarco, Bernard C. Lesieutre
benchmark similarity 0.59
Abstract · 10 pages, 2 figures, 6 tables. Submitted to the IEEE Open Access Journal of Power and Energy. Cases: https://doi.org/10.5281/zenodo.23814538…

This paper documents and checks EPIGRIDS, seven open synthetic transmission grid cases from four independently built networks, made with an optimization-based construction method instead of the graph-statistics method behind most large public synthetic grids. The cases range from 250 to 78,484 buses, with geolocated substations, voltages up to 765 kV, and line parameters taken from conductor data. Each ships under an open license in three common power flow formats that agree at the solved operating point, and the six larger cases have a companion hourly, bus-level load series for one year. The Texas, Florida, and Michigan, Ohio, and Indiana cases are sub-networks of the Eastern case. Every case solves an alternating-current power flow from its stored operating point. With parallel circuits merged, the Eastern and Western cases are 9 and 16% denser than the real interconnections, while graph-statistics cases on the same footprints lie within 6% and meet more published realism criteria. A full single-outage contingency analysis completes on every case, and in an optimal power flow benchmark every case except the New England base case and one of its 12 operating points solves in polar form.

0.31

Which wind and solar modelling choices matter? Effects on capacity factors, energy droughts and European power system configuration

eess.SY ·2026-10-29 ·L. Karkossa, A. Grochowicz, M. J. Koivisto, A. Hahmann, M. VIctoria
similarity 0.55
Abstract

Europe's future power system will rely heavily on wind and solar power and must remain resilient during prolonged periods of low wind and solar generation, known as variable renewable energy (VRE) droughts. To capture such rare events, adequacy assessments increasingly draw on decades of weather data, but the conversion of weather into power is largely treated as fixed. It remains unclear which modelling choices in this conversion matter for representing these droughts, and whether they matter as much as the weather itself. Here we systematically compare these choices side by side (bias correction, wind speed extrapolation, capacity layouts, turbine and photovoltaic configurations, and wake losses) and trace their effects through VRE droughts to the design of a net-zero European power system, using 85 years of reanalysis data. We find that modelling choices barely change how often VRE droughts occur or when the system is stressed. They do, however, determine how much capacity is needed to withstand that stress. By altering the electricity delivered during droughts, they shift required capacity by up to 480 GW, which is comparable to the spread across the most critical weather years. Modelling exercises should therefore use multiple weather years; bias-correct and regionally validate weather inputs; explicitly represent resource heterogeneity, forward-looking technologies, and wake losses; and judge these choices by their effect on the low-generation tail, not only on the mean.

0.24

KPG193-ext: A Synthetic Korean Power Grid Test System for Stability Analysis

eess.SY ·2026-11-09 ·Sungyoon Song, Geonho Song, Min-han Yoon, Yong-Hyun Song, Seung Wan Kim +1 more
similarity 0.55
Abstract

Growing shares of inverter-based generation and constrained transmission expansion increase the need to assess stability across operating conditions. Production-cost models provide chronological commitment and dispatch, but stability analysis requires corresponding electrical detail and device dynamics. This paper introduces KPG193-ext, an extension of the synthetic Korean power-grid test system KPG193 that links chronological operating points with detailed electrical and dynamic models. The extension adds synchronous-machine, controller and renewable-converter models, together with explicit voltage levels, generation terminals, inter-voltage and step-up transformers, and reactive compensation. The resulting 731-bus network retains the original 193 regional locations. Daily unit commitment followed by hourly AC optimal power flow establishes 8,760 operating points for 2025, each distributed as paired steady-state and dynamic-model files. Selected-hour studies examine generation-loss frequency response, steady-state flow-voltage characteristics, and rotor-angle response with special protection system actions. The results reveal differences in delivered frequency support, internal voltage stress along regional transfer paths, and the angle-frequency tradeoff of corrective generator tripping. The database provides a common basis for examining the stability implications of commitment, dispatch and corrective action across daily and seasonal operating conditions.

0.32

Benchmarking a Grid Foundation Model for AC Optimal Power Flow: Feasibility and Warm-Start Results on Synthetic Texas and South Carolina Grids

eess.SY ·2026-11-17 ·Tam Kemabonta, Brighton Ombuki, Vladimir Abdelnour
similarity 0.54
Abstract · 5 pages, 3 figures, 2 tables. Submitted to the 2027 IEEE PES General Meeting

Learning-based surrogates for alternating-current optimal power flow (AC-OPF) are often judged by the gap between their objective value and that of a nonlinear solver, which does not show that a prediction satisfies power balance and network limits. This paper tests whether predictions from the pretrained foundation model GridSFM-Open 1.1.0, recently released by Microsoft, are feasible AC-OPF operating points and whether they are useful initial values for a nonlinear solver. The model was evaluated zero-shot and after fine-tuning on 10, 100, and 1,000 labeled scenarios (FT10, FT100, and FT1000) on 500 scenarios for each of two synthetic grids, ACTIVSg2000 (Texas) and ACTIVSg500 (South Carolina), with Ipopt, MATPOWER MIPS, and pandapower PIPS as solver references. The lowest Texas median cost gap, 0.44\% for FT100, coincided with thermal violations in 24.1\% of cases and a median maximum bus power mismatch of 89 MW and 197 Mvar. Texas zero-shot predictions had a median maximum mismatch of 648 MW and 1,641 Mvar, and every South Carolina case violated a thermal limit for every model variant. Seeding Ipopt with FT1000 predictions gave geometric-mean solve-time speedups of 1.55x on South Carolina and 1.12x on Texas (p = 0.06, not significant at the 5\% level), while zero-shot seeds slowed South Carolina solves (0.26x). A small objective gap therefore did not indicate feasibility: although median zero-shot inference took only 1.32 s on Texas and 0.157 s on South Carolina on a shared host, every prediction still required a nonlinear solver, and fine-tuned predictions gave modest, grid-dependent warm-start speedups while zero-shot predictions slowed convergence on one grid. GridSFM may therefore be useful for initializing a nonlinear solver, but obtaining feasible AC-OPF solutions still required the solver.

0.32

Generalization Testing of Grid Foundation Models for Power Flow and Optimal Power Flow

eess.SY cs.LG ·2026-11-14 ·Ayushi Jolotia, Parikshit Pareek
similarity 0.54
Abstract

There is growing interest in foundation models (FMs) for power grids, particularly for power flow and optimal power flow. Their usefulness depends on generalization accuracy, which existing works test on their own benchmarks. We propose a three-axis framework to test their generalization limits: changed admittance matrices of training grids, load levels, and unseen grids. We test GENCO, LUMINA and GridSFM against the DC baseline, alongside their reported limitations, and discuss theoretical reasons for their failures. Experiments reveal that adding a line degrades all FMs more than removing one, and longer lines eventually make LUMINA and fine-tuned GENCO worse than DC. All three degrade beyond their training load range, where the loading-voltage curve steepens. On unseen grids, LUMINA degrades sharply even inside its training range, and GridSFM fails on the grid farthest from it. Thus, beyond training conditions, FMs behave more like meta-models requiring test-time fine-tuning data and compute.

0.24

DER-Fault: A Simulation-Based Fault Dataset for DER-Integrated Distribution Systems Under Diverse Operating Conditions

eess.SP ·2026-09-28 ·Fathima Razeeya Mohamed Razick, Petr Musilek
similarity 0.53
Abstract · 10 pages, 4 figures, Associated dataset available on Zenodo

The growth of distributed energy resource (DER) integration introduces greater variability in distribution system operating conditions, creating a need for comprehensive datasets for developing and evaluating data-driven fault diagnostic methods. This paper presents \textbf{DER-Fault}, a simulation-based dataset generated in OpenDSS using the Iowa 240-bus distribution system with photovoltaic (PV) generation, electric vehicle (EV) charging, and vehicle-to-grid (V2G) operation. To capture annual load variability while maintaining a manageable number of simulation cases, 60 representative operating conditions are selected from 8,760 hourly load profiles, covering peak, off-peak, transition, typical weekday, and typical weekend conditions. Six DER scenarios with varying PV and EV penetration levels and V2G participation are considered. The dataset includes normal operation and ten short-circuit fault classes, with varying fault resistance. Pre- and post-fault voltage and line-current phasor measurements are recorded at selected measurement locations, resulting in 19,800 simulation cases. Technical validation demonstrates broad coverage of annual loading and DER operating conditions, distinct phase-specific responses corresponding to the simulated fault types, and a consistent reduction in voltage-phasor disturbance with increasing fault resistance. The resulting dataset provides a structured resource for developing and evaluating machine-learning and other data-driven methods for fault detection, classification, and localization in DER-integrated distribution systems.

0.26

Reliability Value of Long-Duration Energy Storage against Extreme Events in High-Renewable Grids: A Full-Year AC-OPF Assessment

eess.SY ·2026-09-06 ·Jeongdong Kim, Jonggeol Na, Sungho Shin
similarity 0.53
Abstract · 39 pages, 12 figures

Long-duration energy storage (LDES) can mitigate prolonged renewable--load imbalances during Dunkelflaute events, but existing studies rely on zonal or linearized DC network models and inadequately analyze the operational feasibility of the grid across a wide range of full-year renewable, load, and contingency scenarios. To address this gap, this paper introduces a multi-period alternating-current optimal power flow (AC-OPF) formulation that captures the full nonlinear network physics and assesses the reliability value of LDES in high-renewable grids. To evaluate scarcity events spanning multiple days to weeks, full-year operation is modeled as an 8,760-h load-shedding minimization over scenarios sampled from a Gaussian copula model, fitted to 2010--2025 historical wind and bus-level load data, that represents both typical variability and tail events. On a synthetic 200-bus Illinois transmission network, a hybrid fleet of battery energy storage (BESS) and LDES with 50 MW total power reduces annual load shedding by 83.0% on average relative to the base network, versus 68.5% for short-duration BESS alone at equal power. To further account for unexpected line outages throughout the year, the formulation is extended to a multi-day security-constrained AC-OPF. Under N-1contingencies, no feasible operating solution is obtained for the base network, whereas the LDES-equipped network remains feasible in all considered cases, thereby saving the cost of additional generation and transmission capacity. During the contingency period, LDES acts as a backup power supply, requiring only 5.5% more generation on average than the no-contingency base case.

0.21

Grid-Compliance Testing of Wind Turbines through Virtualized Component Tests: Testing Concept and Test Bench

eess.SY ·2026-11-13 ·Simon Moritz, Yoga Viknesh Kannan, Florian Andresen, Laura Fuentes Grau, Manuel Fischer +11 more
published similarity 0.52
Abstract · 10 pages, 7 figures, 5 tables, peer-reviewed journal article

As the proportion of inverter-connected wind turbines increases, test methods for evaluating their grid behavior are becoming increasingly important. This paper presents a Power Hardware-in-the-Loop (PHiL)-based method for grid connection testing of wind turbines. For the first time, geographically distributed simulations of aerodynamics via the Internet and of the grid model via a fiber-optic connection are integrated into certification-relevant tests. The concept expands upon the methods described in IEC TS 61400-21-4. Initial experimental results confirm high emulation quality and sufficiently low latencies, and meet the requirements for a standards-compliant grid emulation.

0.37