CS Paper Radar

Phase-Compensated Frequency-Scan Measurement of Harmonic Transfer Function Impedance

Yiyang Liao, Yitong Li, Jinjun Liu

eess.SY ·submitted 2026-10-28 08:32 UTC · v1

Abstract

Impedance models obtained through frequency scanning provides terminal characterization for small-signal stability analysis without requiring detailed knowledge of internal converter parameters. When unbalanced steady-state components introduce cross-frequency coupling, conventional $2\times2$ impedance scan methods must be extended to identify harmonic transfer function (HTF) impedance. However, the measured phases of frequency-coupling terms depend on the starting time of the fast Fourier transform (FFT) window, potentially introducing phase errors when different time references are used. This paper presents a $dq$-domain measurement method of HTF impedance that explicitly accounts for this time dependence. Phase compensation aligns the measured Fourier coefficients to a common electrical phase reference, correcting the resulting phase discrepancies and enabling consistent impedance reconstruction. Comparisons with analytical models under balanced and unbalanced conditions verify the measurement method, recovering the conventional $2\times2$ impedance and the dominant coupling blocks of a $6\times6$ HTF representation, respectively.

Closest papers

Nearest neighbours by meaning across the whole index.

Identification of $dq$-Asymmetric Impedances as Complex Transfer Functions Using a Single Arbitrary Excitation

eess.SP eess.SY ·2026-08-30 ·Mohamed Abdalmoaty, Zheran Zeng, Dongsheng Yang, Florian Dörfler
similarity 0.61
Abstract

Cross-coupling between the $dq$ coordinates makes the identification of asymmetric grid impedances a challenging problem, particularly near the fundamental frequency where the asymmetric coupling is strongest. Existing schemes usually handle it either by perturbing the two coordinates sequentially, which lengthens the measurement, or by using a time-domain method with a global parametric model whose order must be tuned. This paper develops a single-shot active non-parametric frequency-domain method that avoids both. The equivalent impedance is parameterized by a pair of single-input single-output complex transfer functions. Each spectral line is fitted with a local rational model; the leakage and transient contributions are estimated, so that neither periodic steady-state excitation nor repeated excitation cycles are required. We give the exact finite-time discrete Fourier transform relation for the conjugate-coupled complex-signal model, and analyse the distortion that a stationary-frame filter placed ahead of the Park transform imposes on the identified pair. The method is validated on a controller hardware-in-the-loop platform against an analytically derived small-signal model, for a symmetric grid and for the same grid with an added grid-following converter that renders it asymmetric. Both complex transfer functions and all four real transfer functions of the $dq$ impedance are recovered over a wide band from a single one-second record of a random excitation, at 1 Hz resolution.

0.26

Equivalent DQ Sequence-Domain Model of Unbalanced Three-Phase Passive Elements for Power Converter Controllers

eess.SY ·2026-09-01 ·Air\án Franc\és, Luis Saz, Rafael Castillo, Dionisio Ramirez, Javier Uceda
publishedtheoryhighly cited similarity 0.56
Abstract · 8 pages, 7 figures, 2023 IEEE Applied Power Electronics Conference and Exposition (APEC)

Equivalent dq0 models of three-phase passive impedances are widely used for the design of three-phase inverter and rectifier controllers in the synchronous frame. However, these equivalent models assume that the impedance in each phase are the same, which is not always applicable. The fact that the impedance in each phase is different, generates second order harmonic content in the dq0 components, which hinders the advantages of the dq0 transformation. To avoid the second harmonic in these scenarios, it is possible to use the Fortescue's theorem to represent any asymmetrical set of three-phase signals as a linear combination of three symmetrical sequences. In the literature, only a few works have attempted to derive the equivalent model of unbalanced three-phase passive elements in the sequence domain, and none is able to account for the interaction between the zero sequence and the positive and negative sequences. This work presents the derivation of the equivalent dq sequence-domain model of unbalanced three-phase passive elements both analytically and with an intuitive graphical approach. Experimental results are shown to validate the proposed models.

0.73

Passive Identification of Unequal Phase Grid Impedances by Phase-Domain Source Cancellation

eess.SY ·2026-10-28 ·Songyang Zhang, Xun Gong, Bo Cao, Reza Iravani
similarity 0.56
Abstract

Passive grid impedance estimators that return a single resistance--inductance pair cannot represent a grid whose phase impedances are unequal. This paper identifies a separate pair for each phase from recorded point-of-common-coupling (PCC) voltage and current without injected perturbations. In each phase, the unknown grid-source voltage is cancelled by a periodic difference (PD) or by a second-order-generalized-integrator notch difference (SOGID), and moving-window integration (MWI) replaces the current derivative by an integral and an endpoint feature. The resulting two-parameter regression requires a period or notch-frequency estimate but no phase-locked-loop angle. A voltage-balance analysis gives the source residual left by frequency mismatch and bounds the parameter error by the ratio of this residual to the conditioning of the two features. In the unequal-phase interval (8.3--9.8~s) of a 10-s EMTP grid-forming record, SOGID-MWI attains phase-averaged R/L errors of 5.09/0.33\%; a shared value has a minimum error of 41.67\% for the phase ratio 1:0.5:2. On a 50-s constant-impedance grid-following record, the errors are 0.56/0.06\% over the 20--30-s synchronization disturbance. In a controlled 40-dB noise study, a noise-referenced update rule reduces the white-noise GFL error from 55.9/65.0\% to 12.3/11.5\%.

0.34

Frequency-Frame Covariance for Reactive-Power Scalarization

eess.SP eess.SYmath-ph ·2026-11-04 ·Kai Sun
similarity 0.53
Abstract

Measured voltage and current waveforms may be represented in a reference frame whose frequency differs from the physical fundamental frequency. Reactive-power readouts calculated from such frequency-shifted coordinates may change if their readout operators are not transformed consistently. This paper presents a frequency-frame covariance formulation for finite-spectrum, zero-mean periodic waveforms with complete harmonic information over one physical period. A necessary and sufficient covariance condition is derived, requiring the readout operator to transform consistently with the waveform representation. Consequently, frequency-dependent harmonic weights must be evaluated at physical harmonic orders rather than relative frame labels. In particular, the derivative/Iliovici readout equals a relative-derivative contribution plus an explicit reference contribution. The formulation also separates readout-operator errors from errors caused by changes in the physical components retained by waveform projections. Three analytical cases illustrate conditional carrier recovery for a memoryless resistor, physical-frequency weighting at relative zero in an RLC branch, and the possibility that an exact reactive-power scalar can coexist with a substantial waveform error after projection. The scope is deterministic calculation consistency in frequency-shifted coordinates rather than instrument measurement uncertainty.

0.13

A New Index for Quantifying Stability Adaptation Effort in Power Electronics-Dominated Power Systems Based on Frequency-Domain Impedance Identification

eess.SY ·2026-10-02 ·Luis A. Garcia-Reyes, Macarena Martin-Almenta, Edgar Nuño-Martínez, Javier Renedo, Antonio Cordón-Rodríguez +2 more
published similarity 0.51
Abstract · Paper in Proceedings of CIGRE Paris Session, C4-PS1, Paper ID 11553

The increasing use of converter based resources has made stability assessment in modern power systems more challenging, particularly because many devices are available only as black box models. Conventional eigenvalue based methods require full dynamic representations, while frequency domain impedance techniques based on the Generalized Nyquist Criterion (GNC) provide stability insight but do not quantify how much a converter must be retuned to restore stability. This paper introduces the Adaptation Effort Index (AEI), a metric that measures the sensitivity of dominant modes to parameter variations and quantifies the effort required for a converter to reconfigure itself under unstable operating conditions. The AEI combines the Nyquist Stability Margin obtained from frequency domain screening with a modal sensitivity index derived from fitted state space models synthesized from black box impedance data. The method is applied to a system comprising a grid forming and a grid following converter. Results show that, although both units can be tuned to stabilize the system, the grid following converter requires significantly less adaptation effort. The AEI therefore provides a practical and model agnostic tool for identifying which converter should be reconfigured in converter dominated grids, offering valuable guidance for system operators and manufacturers.

0.30

Impedance-Based Sensitivity Analysis for Stability Enhancement of LCC-HVDC Links Connected to Weak Grids Using Grid-Forming Converters

eess.SY ·2026-09-09 ·Luis A. Garcia-Reyes, Anup Joshi, Javier Renedo, Macarena Martin-Almenta, Oriol Gomis-Bellmunt +3 more
benchmark similarity 0.51
Abstract · Best Paper Award in the 2026 5th IEEE International Conference on Power Systems and Electrical Technology

This paper presents a frequency-domain, impedance-based sensitivity methodology for stability assessment and enhancement of line-commutated converter HVDC (LCC-HVDC) links operating under weak-grid conditions. The methodology integrates frequency-domain identification tailored for black-box systems, the Generalized Nyquist Criterion (GNC) for multivariable stability assessment, and modal impedance decomposition with participation-factor analysis to locate and interpret interaction mechanisms. The approach is validated against a detailed linearized state-space model and nonlinear EMT simulations of an LCC-HVDC benchmark. A sensitivity study varying the grid short-circuit ratio (SCR) reveals a stability limit for the standalone LCC-HVDC link and demonstrates that the integration of a grid-forming voltage source converter (GFM-VSC) substantially increases the stability margin.

0.20

Decentralized Impedance Specifications for Grid-Connected Converters: a Sequence-Domain Gershgorin Method, and a Frequency-Wise Framework for Combining Different Criteria

eess.SY ·2026-11-03 ·Lazar Stojanović, Ružica Cvetanović, Paolo Mattavelli, Simone Buso
similarity 0.49
Abstract

In complex grid scenarios, with many power electronics (PE) converters connected, having specifications for converters can ease the design process. A practical approach is to impose the specifications on the converter's small-signal impedance in the frequency domain. This is advantageous since impedance is a physical property that can be measured. This paper focuses on providing decentralized impedance specifications for each converter connected to an ac bus. With decentralized specifications, each converter has its own specifications, which are independent of other converters' impedance. This enables a competitive multi-vendor environment while guaranteeing system stability. Existing methods of imposing decentralized specifications, based on the small-gain, passivity and Gershgorin theorems, are formulated within a common frequency-domain framework. Building on this, two new solutions that reduce the conservativeness of the specifications are proposed. First, Gershgorin-based decentralized specifications are formulated in the modified sequence domain. Second, a framework for combining different specification types across frequency ranges is developed and mathematically proven. The methods are compared on examples covering sub-synchronous and harmonic-range interactions of grid-following converters, grid-forming converters, and a mixed grid-forming/grid-following system, using analytical models, black-box impedance measurements, and time-domain responses obtained from simulations and an experimental setup.

0.24

Comparative Assessment of Frequency Scans using EMT and RMS Models

eess.SY ·2026-08-27 ·Clea Bürgel, Gustavo Valverde, Gabriela Hug
similarity 0.48
Abstract

Frequency scans of inverter and grid impedances are crucial for assessing small-signal stability and system strength in inverter-dominated power systems. This paper compares frequency-scan results for several generating units, including a synchronous generator, grid-following, and grid-forming inverters, using fully dq electromagnetic transient and root-mean-square (RMS) models in Simulink. The scans are performed for the same device rating and operating point. Frequency scans and time-domain simulations show that the RMS models are valid only at low frequencies. We find that the current-controlled grid-forming inverter is more difficult to represent in RMS than the voltage-controlled grid-forming inverter. However, including the inner voltage-control loops improves the accuracy of the RMS representation. The paper also investigates the influence of generator and grid impedance on the total system impedance seen from the point of common coupling and relates the oscillatory modes and zeros of the system to peaks and dips in the first and second singular values of the system impedance, respectively.

0.22