LC-Resonance Placement Limits and Damping Recovery in Virtual-Admittance-Based Grid-Forming Inverter Control

Stephen Arinze Obi, Jae-Jung Jung

eess.SY ·submitted 2026-10-29 12:50 UTC · v1

Abstract

Compact LC-filter design and inner-loop control must be coordinated for stable grid-forming operation. This paper quantifies how current-loop proportional gain constrains LC-resonance placement in virtual-admittance-based dual-loop control with unity voltage-feedback decoupling (VFD) and capacitor-voltage active damping. Equivalent-impedance analysis identifies gain-dependent contraction of the positive-resistance region. Delayed inverter-current feedback opposes VFD-assisted damping above one-sixth of the sampling frequency. Simple proportional-path frequency shaping recovers an admissible effective-gain window while retaining unity VFD and leaving the resonant path unchanged. Reduced-model criteria, checked against the complete model, link window closure to a nominal resonance-placement limit near one-third of the sampling frequency under single-sampled single-update operation over the studied gain range. A 3-kVA prototype demonstrates an 83.3% LC-product reduction at comparable voltage and nominal current crossovers. A separate comparison with the same high-resonance filter demonstrates stable operation at 2.68 times the unshaped nominal current crossover. Output-impedance analysis and grid-connected tests identify additional grid-dependent gain constraints.

Comment
10 pages

Closest papers

Nearest neighbours by meaning across the whole index.

Internal-Model-Control-Based Virtual Admittance Emulation for Enhanced Grid-Forming Performance

eess.SY ·2026-09-18 ·Ruzica Cvetanovic, Lazar Stojanovic, Paolo Sbabo, Paolo Mattavelli, Massimo Bongiorno
similarity 0.65
Abstract

The large-scale integration of renewable energy into electrical power systems places a growing reliance on grid-forming converters (GFMs) to overcome critical stability and control hurdles. By emulating a slowly varying voltage source behind a tunable resistive?inductive impedance, GFMs enable precise setpoint tracking and vital grid support. In this regard, virtual admittance (VA)-based inner-loop control provides exceptional flexibility in shaping the converter's small-signal immittance at connection terminals, allowing for advanced GFM functionalities. This article addresses a novel internal-model-control-based VA approach, which inherently accounts for the effects of the inner current-control loop and the voltage feedforward. Unlike the state-of-the-art VA control, the proposed VA control ensures that, at frequencies outside the influence of outer loops, the converter's terminal admittance closely matches the target admittance, which is shown to be relevant for stability. It is revealed how, with the state-of-the art VA control, a small-signal instability in the harmonic range may arise if a low-pass filter with a high cut-off frequency is used for the voltage feedforward. However, the proposed VA control ensures stable operation regardless of this cut-off frequency. The methodology is experimentally validated using a laboratory prototype that features three-phase voltage-source converters.

0.21

Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected Inverters

eess.SY ·2026-10-23 ·Runnan Wang, Wanrong Li, Huawei Yuan, Sinan Li
published similarity 0.61
Abstract · Accepted at the 2026 IEEE PES Australasian Universities Power Engineering Conference (AUPEC)

Grid-connected inverters can be unstable when their current-control loops interact with an uncertain external network. Returning the existing controller to improve damping also alters current tracking because tracking dynamics and output admittance are coupled. This paper adds a local model-free control (MFC) loop around the existing current controller to reduce output admittance while closely preserving nominal current-tracking dynamics. The added loop uses local inverter parameters without an external grid or neighbouring converter model. A Norton formulation separates reference tracking from the current response to terminal-voltage disturbances and establishes a tracking-preservation condition for admittance reshaping. Reducing the disturbance response makes the inverter behave more like an ideal controlled current source. Averaged-model simulations show reductions exceeding 65% in the magnitudes of all four dq output-admittance elements over 10-200 Hz, with closely preserved current-tracking dynamics. Generalised Nyquist analysis predicts small-signal stability for all sampled grid-impedance cases with MFC, compared with 90.0% without MFC.

0.28

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.57
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.26

Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

eess.SY ·2026-10-20 ·Amir H. Abolmasoumi, Hamed Mohsenian-Rad
published similarity 0.55
Abstract · Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

0.29

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.54
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

Impedance-Based Sensitivity Analysis for Stability Enhancement of LCC-HVDC Links Connected to Weak Grids Using Grid-Forming Converters

eess.SY ·2026-09-09 ·Luis A. Garcia-Reyes, Anup Joshi, Javier Renedo, Macarena Martin-Almenta, Oriol Gomis-Bellmunt +3 more
benchmark similarity 0.54
Abstract · Best Paper Award in the 2026 5th IEEE International Conference on Power Systems and Electrical Technology

This paper presents a frequency-domain, impedance-based sensitivity methodology for stability assessment and enhancement of line-commutated converter HVDC (LCC-HVDC) links operating under weak-grid conditions. The methodology integrates frequency-domain identification tailored for black-box systems, the Generalized Nyquist Criterion (GNC) for multivariable stability assessment, and modal impedance decomposition with participation-factor analysis to locate and interpret interaction mechanisms. The approach is validated against a detailed linearized state-space model and nonlinear EMT simulations of an LCC-HVDC benchmark. A sensitivity study varying the grid short-circuit ratio (SCR) reveals a stability limit for the standalone LCC-HVDC link and demonstrates that the integration of a grid-forming voltage source converter (GFM-VSC) substantially increases the stability margin.

0.20

Comparative Assessment of Frequency Scans using EMT and RMS Models

eess.SY ·2026-08-27 ·Clea Bürgel, Gustavo Valverde, Gabriela Hug
similarity 0.53
Abstract

Frequency scans of inverter and grid impedances are crucial for assessing small-signal stability and system strength in inverter-dominated power systems. This paper compares frequency-scan results for several generating units, including a synchronous generator, grid-following, and grid-forming inverters, using fully dq electromagnetic transient and root-mean-square (RMS) models in Simulink. The scans are performed for the same device rating and operating point. Frequency scans and time-domain simulations show that the RMS models are valid only at low frequencies. We find that the current-controlled grid-forming inverter is more difficult to represent in RMS than the voltage-controlled grid-forming inverter. However, including the inner voltage-control loops improves the accuracy of the RMS representation. The paper also investigates the influence of generator and grid impedance on the total system impedance seen from the point of common coupling and relates the oscillatory modes and zeros of the system to peaks and dips in the first and second singular values of the system impedance, respectively.

0.22

Comparison of Current-Limiting Strategies for Grid-Forming Converters Under Grid Faults

eess.SY ·2026-10-17 ·Maitraya Avadhut Desai, Ramona Stoll, Xiuqiang He, Florian Dörfler, Gabriela Hug
published similarity 0.53
Abstract · Presented at the 16th IEEE PowerTech Conference (Kiel 2025). 6 pages, 12 figures

This paper investigates the performance of three state-of-the-art current-limiting strategies for grid-forming (GFM) converters under grid faults. These highly effective strategies include virtual admittance control, virtual admittance control enhanced with virtual power feedback, and the recently developed cross-forming control. The performance comparison addresses two crucial requirements for GFM converters under grid faults, namely transient stability and reactive current injection. The comparison indicates that the virtual admittance control enhanced with virtual power feedback shows the most promising transient stability performance, while the cross-forming control exhibits superior reactive current injection performance. Thus, individual benefits of each strategy can be obtained by properly combining them.

0.32