CS Paper Radar

Passivity Control for Synchronous Machine Systems using Battery, Field Current and Governor Actuation

Maryam Khodabakhshloo, Elizabeth L. Ratnam, Ian R. Petersen

eess.SY ·submitted 2026-11-17 22:57 UTC · v1

Abstract

The passivity of synchronous machines enables power system stability to be established from local conditions. A recent state-feedback design enforces robust passivity using battery actuation at the machine terminal bus. This paper extends that design to a model that includes the field winding and the dynamics of a steam turbine and its governor. The extended model provides two additional actuator signals: the exciter input and the governor input. The nonlinear terms in the model depend on speed and field current deviations, and are represented as bounded uncertainties. Robust positive real conditions are derived in terms of a single algebraic Riccati equation. From its solution, a state-feedback controller is designed in closed form. Numerical results show that, unlike the design with battery actuation alone, the proposed controller leads to passivity at all loading levels when the damping is low.

Closest papers

Nearest neighbours by meaning across the whole index.

State-Feedback Passivity Control for Synchronous Machine Systems

eess.SY ·2026-11-05 ·Maryam Khodabakhshloo, Elizabeth L. Ratnam, Ian R. Petersen
similarity 0.80
Abstract

The passivity of a generating station enables network stability to be established from conditions verified locally at each station. For synchronous machines, however, passivity can only be certified under conditions on the operating point, and these conditions fail under heavy loading and weak damping. This paper develops a state-feedback controller that enforces passivity using a storage battery connected at the terminal bus. A bilinear term arising from the product of the rotor-speed and stator-current deviations is treated as a bounded uncertainty, leading to robust positive-real conditions that can be enforced by a state feedback control designed using a single algebraic Riccati equation. The resulting controller guarantees passivity whenever the Riccati equation admits a positive-definite solution, with no separate condition on the operating point. Numerical examples show that existing conditions certify passivity only up to a fraction of the rated current, whereas the proposed state-feedback approach certifies it at the rated operating point of the machine.

0.28

Passivity-Based Nonlinear Control

eess.SY ·2026-08-15 ·Pablo Borja
published similarity 0.53
Abstract · 23 Pages, 2 figures

The passivity-based control (PBC) framework focuses on understanding and modifying the energy storage and dissipation in the system to be controlled. To this end, PBC techniques often proceed in two steps: (i) ensuring that the closed-loop system's energy is minimum at the desired point, and then (ii) forcing the system to dissipate energy until reaching that point. These control methods have proven effective in controlling a wide range of systems, especially physical ones, even when they exhibit highly nonlinear behaviors. This chapter discusses the main aspects of some PBC strategies for nonlinear systems.

0.28

Guidelines for the implementation of power oscillation damping controllers in power converters

eess.SY ·2026-09-02 ·Javier Renedo, Macarena Martín Almenta, Sergio Martínez Villanueva, Agustín Díaz-García, Antonio Cordón +1 more
similarity 0.50
Abstract

One of the most effective ways to damp electromechanical oscillations in power systems is by means of supplementary controllers attached to the different devices in the power system is by means of power system stabilizers (PSS) in synchronous machines or by means of power oscillation damping (POD) controllers in facilities with power converters. In the recent years, the use of POD controllers in voltage source converters (VSCs) with grid-following (GFL) control has been investigated. Although the potential of POD controllers to help to damp inter-area oscillations in power systems is enormous, their correct implementation is not trivial, because their effectiveness is strongly linked to their settings. This paper provides guidelines for the implementation of POD controllers in power converters for application in real-world power systems. The paper proposes compliance criteria for POD controllers using a synthetic test system and a systematic methodology used in Spanish technical standard for monitoring compliance (NTS), considering practical considerations. The paper also includes numerical examples to illustrate compliance criteria for POD controllers in a synthetic test system. A generic power converter with grid-following (GFL) control is used for the analysis by simulation and POD controllers using modulation of active-power injection (POD-P), reactive-power injection (POD-Q) or both simultaneously (POD-PQ) will be analysed. Results were validated in a large-scale power system. The paper concludes that by using appropriate synthetic systems, methodologies and compliance criteria, POD controllers in power converters could be effective to damp electromechanical oscillation in large-scale power systems.

0.33

On the Achievable Inertia Constant of Inverter Based Resources

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.48
Abstract · Under Review in IEEE Transactions on Power Systems

As inverter-based resources (IBRs) displace synchronous generators, the inertia they can actually contribute to the grid becomes a critical planning parameter. Unlike synchronous machines, this contribution is bounded simultaneously by the available energy reserve, the converter power rating combined with voltage ride-through (VRT) obligations, and the inertia-emulation control scheme with its activation delay. This paper derives each bound in closed form and combines them into a unified envelope $\Heff(t,λ,V_g)=\min(\HE,\HP,\HC)$, which uses parameters accessible to the system operator to quantify how much inertia a plant can provide at a given loading $λ$, grid voltage $V_g$, and time $t$ after a disturbance. The analysis shows that below a loading-dependent critical voltage, VRT reactive-current priority does not leave active-current headroom for inertial power injection; that the converter overload ratio $κ$ matters mainly during voltage dips; and that de-loading yields a linear, quantifiable inertia gain, while collocated energy storage (ESS) removes the source-coupling constraint, making grid-following (GFL) and grid-forming (GFM) plants with storage equivalent post-activation, up to the GFL activation-delay discount within short RoCoF measurement windows. Simulations on the IEEE 9-bus system confirm the framework and motivate a two-dimensional inertia capability curve $H(λ,V_{g,\min})$ as a grid-code instrument analogous to the P--Q diagram of synchronous generators.

0.28

Introduction to Passivity-based Control

eess.SY ·2026-08-15 ·Pablo Borja, Romeo Ortega
publishedsurvey similarity 0.48
Abstract · 26 pages, 1 figure

Passivity-based control (PBC) is a nonlinear control design framework that has proven adequate for controlling a wide range of systems, especially physical ones. Their main ingredients are physical quantities such as energy and dissipation, making the control design more intuitive and endowing the controllers with a physical interpretation. In contrast to other, mathematically-based nonlinear control approaches, the energy-based viewpoint and physical intuition of PBC often make this strategy more robust and energy efficient. This chapter provides an overview of PBC, revisiting the basic aspects of this powerful nonlinear control framework and the most common PBC approaches.

0.28

Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers

eess.SY ·2026-11-02 ·Muhammad Hamza Ali, Amritanshu Pandey
similarity 0.47
Abstract

This document presents dynamic models of a transmission network and average models of power-electronic devices and loads in the synchronous $dq$ frame. We model the network in the positive sequence and its synchronous generators with the classical swing equation and a first-order turbine governor. The power-electronic models cover grid-following inverters and AI data centers. Each inverter has a phase-locked loop, a power controller, and a current controller. Each data center connects to the grid through two step-down transformers. Its low-voltage bus feeds an IT load, an induction-motor cooling load, and a constant-impedance load. A double-conversion uninterruptible power supply (UPS) serves the IT load. We model its rectifier, grid-forming output inverter, battery, and bidirectional DC-DC converter. A measured GPU power trace drives the IT demand. We replace every non-smooth operation with a smooth surrogate. This keeps the discretized model continuously differentiable for the nonlinear solver. We also show how we initialize each model at its power-flow operating point.

0.25

State-Dependent Delay Modeling of Wind-Farm Wake Dynamics

eess.SY ·2026-10-27 ·Sengiyumva Kisole, Jungbae Chun, Peter Seiler, Matthew M. Peet
similarity 0.47
Abstract

Turbines convert wind to electrical power. In the wake of a turbine, wind speed is reduced in proportion to the amount of power extracted. In a wind farm, downstream turbines may be located in wake of an upstream turbine, requiring coordination to yield maximum power generation. This paper creates a state-dependent delay model for a two turbine wind farm. The upstream turbine creates a wake that diminishes the wind speed at the downstream turbine. Changing the upstream turbine operation will affect the downstream turbine after a delay that depends on the wind-propagation time between them. This delay depends on the upstream power extraction and it can destabilize the combined dynamics. Conventional models of this effect rely on nonlinear partial differential equations (PDEs). Control design and analysis with such models is difficult with established methods. We first show that the PDE model can be represented by an Abel-type state-dependent delay differential equation. The equation has an implicit solution. To obtain an explicit representation, we then introduce a simplified state-dependent delay model. Both models predict destabilizing interactions between the two turbines. Numerical examples illustrate delay-induced oscillations using the simplified model and verify their effectiveness in simulation.

0.26

Enhancing Grid Stability with Synchronverter-Based Control for Grid-Side Converters in Wind Power Systems

eess.SY ·2026-11-02 ·Alan Valadez, George Weiss, Chunjiang Jia, Chong Ng
published similarity 0.47
Abstract

This paper proposes a new synchronverter control strategy for wind turbine grid-side converters, aimed at bolstering grid resilience by providing essential inertial frequency support without the need for additional energy storage components. The strategy harnesses the inherent energy storage capability of the DC-link capacitor to emulate the dynamic behavior of a synchronous generator, effectively contributing to grid inertia. A dual-controller architecture is implemented, consisting of a slow PI controller to maintain DC voltage stability and a fast protection mechanism to prevent overvoltage and undervoltage excursions. Critically, the control scheme facilitates controlled reductions of up to 10% in the DC-link voltage, generating a power reserve that can be strategically deployed for inertia emulation while preserving safe operating limits. The efficacy of the proposed method is validated through simulations of a representative three-turbine wind power plant, incorporating coordinated operation via virtual friction for inter-machine damping and local-global control strategies. Results showcase the superior performance of the proposed strategy compared to conventional grid-following control, emphasizing its potential to significantly improve grid stability and address the increasing challenges posed by high renewable energy penetration.

0.62