CS Paper Radar

Travelling-Wave-Based Protection of DC Hubs in Bipolar HVDC Grids

Rahul Rane, Victor Daniel Reyes Dreke, Wilhelm Winter, Aleksandra Lekić

eess.SY ·submitted 2026-11-25 14:24 UTC · v1

Abstract

This paper presents a stationary wavelet transform (SWT)-based method for DC fault detection and classification in a three-terminal bipolar modular multilevel converter (MMC)-based HVDC system with a dedicated metallic return (DMR). The system incorporates DC switching stations (DCSSs) with interconnected DC circuit breakers (DCCBs). The method uses line-mode voltage wavelet detail energy for fault detection and wavelet detail energy derived from pole voltages and DMR current for fault classification, distinguishing pole-to-pole, pole-to-ground, and pole-to-DMR faults. Its performance is evaluated using a real-time hardware-in-the-loop (HIL) platform integrating an real-time digital simulator (RTDS) with embedded processing hardware. Busbar and cable faults with varying fault types, resistances, and locations are investigated. The results demonstrate the feasibility of real-time implementation and characterize the effects of fault location and travelling-wave propagation on transient energy and protection response time. The effectiveness of pole-voltage and DMR-current detail energy features in distinguishing fault types is also evaluated.

Closest papers

Nearest neighbours by meaning across the whole index.

Non-Blocking Fault Current Limiting Control of Half-Bridge MMCs for MTDC Transmission

eess.SY ·2026-08-31 ·Pengxiang Huang, Shahil Shah
similarity 0.64
Abstract

A key protection requirement in multiterminal HVDC (MTDC) transmission systems is to selectively isolate faulted areas using DC circuit breakers (DCCBs) during DC faults while keeping the rest of the systems in operation. However, in MTDC systems using half-bridge modular multilevel converters (HB-MMCs), the lack of inherent fault current suppression capability in HB-MMCs can cause converter blocking before fault clearance by DCCBs. This work presents an active fault current limiting (AFCL) control strategy for HB-MMCs to mitigate DC fault currents, thus avoiding converter blocking and reducing the breaking capability required of DCCBs. In addition, a systematic approach is proposed to design the AFCL control strategy under converter and network stability constraints. The effectiveness of the proposed strategy is demonstrated through PSCAD on two typical MTDC systems during DC faults.

0.20

Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systems

eess.SY ·2026-11-02 ·Alexander Novikov, Luis A. Garcia-Reyes, Anup Joshi, Ahmar Farooque, Junaid Khalid +1 more
published similarity 0.57
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

The decarbonization of the energy sector, driven by the Paris Agreement and the European Green Deal, is increasing the share of renewable energy sources (RES) in power systems. Unlike traditional systems, RES-based systems rely on power electronic converters, which creates unprecedented challenges for reliability and resilience. The future power system is expected to combine a low-level AC layer with an upper-level High Voltage Direct Current (HVDC) backbone, which requires new understanding of fault protection, stability, and interaction between AC and DC components, as well as new models and simulation tools. This is especially critical in systems moving towards 100 percent converter-based generation. Protection systems detect, locate, and isolate faults to protect assets while the rest of the system keeps operating. Traditionally, they rely on the large fault currents supplied by synchronous machines. In modern systems, converter controls limit the fault current contribution to about 120 percent of rated current, so relays that distinguish faults from normal overcurrents based on current level may operate incorrectly. In addition, inverter-based resources (IBR) may not inject enough negative and zero sequence current for directional relays to work properly, and converters hold the voltage at a fixed value only within their reach, beyond which it drops quickly. As a result, existing protection schemes may not provide the expected accuracy and reliability. This report reviews the protection challenges identified in recent academic literature for power systems with high shares of converter-based resources. It covers the specific characteristics of RES, the challenges for protection with intelligent electronic devices (IED), the challenges of converter control during faults, and the main solutions proposed in research over the last decade.

0.49

A Cost-Effective Submodule with Fault-Blocking Capability for Modular Multilevel Converters

eess.SY ·2026-11-05 ·Yu Liu, Shengbo Zhang
similarity 0.55
Abstract · 11 pages, 22 figures

Modular multilevel converter (MMC) has become an attractive technology for high-power electronics applications thanks to its high energy efficiency, high power rating, high modularity, flexible scalability, and superior output waveform quality. It has attracted considerable research attention, and numerous submodule (SM) variants have been developed for different objectives. Among them, the half-bridge SM (HBSM) is the most widely adopted thanks to its simplicity, but it cannot interrupt DC-side short-circuit currents. Various SM topologies with fault-blocking capability have been proposed. These SM topologies contain additional switches and passive components compared to the HBSM, leading to higher capital and operating costs. Aiming at these issue, an SM topology capable to block DC-side fault-currents with a reduced component count is proposed in this paper. The proposed SM includes two variants, one employs only two fully-controlled switches. An operation and control scheme for the proposed SM are also developed and presented in the paper. The functionality of the proposed SM is validated by experiment, and the value of the SM is demonstrated through a test simulation for an high-voltage direct-current (HVDC) transmission system.

0.30

Intelligent Fault and Lightning Detection Algorithm for VSC-MTDC grids based on ResNet with Hybrid Attention Mechanism

eess.SY ·2026-09-08 ·Yunqi Zhang
unusual similarity 0.55
Abstract

To address the existing challenges in fault detection for voltage source converter-based multi-terminal DC (VSC-MTDC) grids, this paper proposes an intelligent fault and lightning detection algorithm based on S transform and Residual Network with hybrid attention mechanism (RWHAM).The DC line double-ended initial current traveling waves (ICTWs) are first converted into time-frequency matrices by performing S transform and then visualized as a two-dimensional image. The image effectively characterizes the time-frequency features of ICTWs under different fault and lightning conditions, making it easier to extract critical features for the models. Next, the RWHAM model is constructed and the images are fed into the model to detect internal and external faults and lightning interference. The weight of the key information in the image is increased by hybrid attention mechanism, which in turn improves the fault detection ability of the RWHAM model. Extensive simulations involving 21,620 distinct cases on PSCAD/EMTDC validate the algorithm's high accuracy and rapid response across different types of faults and lightning interference. Furthermore, it exhibits excellent generalization ability when the parameters of VSC-MTDC grids change.

0.26

Data-driven current control of modular multilevel converter-based HVDC transmission system

eess.SY ·2026-11-05 ·Victor D. Reyes Dreke, Rahul Rane, Aleksandra Lekić
similarity 0.55
Abstract · 8 pages, submitted to IET AC and DC Power Transmission (ACDC)

Model-based design (MBD) is a mature framework for designing the current controllers of modular multilevel converters (MMCs) in high-voltage direct current (HVDC) transmission systems. In MBD, linear state-space models are preferred for their good trade-off between accurate dynamics prediction and simplicity. However, first-principle derivations often neglect relevant MMC dynamics, which can hinder controller performance. Data-driven (DD) methods can deliver less biased models that capture parameter uncertainties, control-loop interactions, and grid dynamics, yet they remain under-exploited for controlling MMC currents. This paper studies DD current control method based on integral Subspace Predictive Control (iSPC), synthesized directly from input--output data measured in a high fidelity real-time digital simulator (RTDS), and proposes an initial guideline outlining the main steps for its systematic application to MMC current control. The proposed iSPC is compared against state-of-the-art DD solution, and the findings are validated through simulation studies in MATLAB/Simulink.

0.32

Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers

eess.SY ·2026-08-27 ·Haoyu Wang, Chi Zhang, Mafu Zhang, Rudy Wang, Peter Barbosa
similarity 0.53
Abstract · Added IEEE submission notice

Solid-State Transformers (SSTs) are increasingly proposed as the interface between distribution grids and data centers due to flexible power flows and fast dynamic response. However, when a short-circuit fault occurs in a load branch, the SST with a voltage-source-type DC-DC stage is forced to shut down due to fault currents. Therefore, current-limiting strategies are strongly needed to prevent catastrophic equipment damage and cascading blackouts by instantly restricting massive current spikes and offering sufficient currents for protection devices to act at the faulted branch. This paper proposes a coordinated DC load fault-tolerant current-limiting and recovery strategy embedded directly in the control of the SST DC-DC stage, avoiding additional hardware cost. Specifically, the fault mechanism of an example LLC resonant converter is studied. Accordingly, a fault detection framework is implemented, a closed-loop current controller is proposed to limit the DC current to a designated value within microseconds by surging the switching frequency and adjusting the duty cycle, and a ramped recovery stage will then restore the DC bus after the fault isolation without inrush currents. Experiments on an LLC converter prototype have verified the feasibility of the proposed current-limiting strategy, enabling faster and lower-cost fault response suitable for resilient data center power architectures.

0.26

Understanding the limits of snapshot-based fault diagnosis in distribution networks

cs.AI ·2026-11-13 ·Ba Tu Phung, Huy Hoang Le, Kim-Anh Nguyen
similarity 0.53
Abstract

Inverter-based resources weaken fault currents in distribution networks, and snapshot-based diagnosis, which classifies a fault from voltage phasors at a few buses at one instant, offers a cheap first-stage screen. Its published accuracies, however, rest on different noise assumptions and do not show whether the error comes from the classifier, the features, the measurement error, or the fault resistance. This paper separates these sources on three IEEE test feeders and a public data set with distributed generation, using four feature sets, thirteen classifiers, and measurement error defined by total vector error classes. The classifier is not the limiting factor, because the full phasor snapshot classifies every fault correctly without noise, and the remaining error comes from measurement error on high-impedance faults. Three voltage sensors classify 90-96% of faults at the 1% accuracy class and 96-99% with distribution micro phasor measurement units (micro-PMUs). A discriminability-margin placement selects them from simulations alone in under one second and matches the best of twelve placement methods. The results show when snapshot-based diagnosis can be trusted.

0.25

Short-Circuit Current Calculation in DC Shipboard Microgrid Using Operational Admittances

eess.SY ·2026-10-30 ·Pietro Cepollini, Fabio D'Agostino, Federico Silvestro, Antonio Chiarelli
published similarity 0.52
Abstract · Accepted and presented at ESARS-ITEC 2026. Copyright 2026 IEEE. Personal use of this material is permitted. Permission from IEEE must be obt…

The increasing adoption of DC shipboard power systems is driven by the need to integrate energy storage systems seamlessly onboard. In this context, accurate calculation of short-circuit current transients is critical for sizing fast-acting protection devices. This paper proposes a methodology to calculate short-circuit current transients based on operational admittance modelling of network elements and power converters. The superposition principle is then applied to calculate current contributions and voltage time profiles. The methodology is validated with a detailed EMT model of a notional LVDC shipboard microgrid section consisting of an active front end, a bidirectional buck-boost converter and two special loads. Results demonstrate that the methodology accurately tracks nodal voltages and the fault current contributions dynamics up to the prospective fault current peak, thus providing a computationally efficient tool for fault analysis and protection coordination in LVDC microgrids.

0.38