Power-Swing Blocking and Out-of-Step Tripping Scheme Using the Swing Center Voltage in Systems With Inverter-Based Resources

Henrik Johansson, Qianli Xing, Jaekeun Lee, Ki-Hyun Kim, Nathaniel Taylor, Xiongfei Wang

eess.SY ·submitted 2026-11-23 13:32 UTC · v1

Abstract

Misoperation of power-swing blocking (PSB) and out-of-step tripping (OST) schemes in distance relays is a critical concern in power systems with increasing penetration levels of inverter-based resources (IBRs). Recently, several papers have studied the impact of IBRs on conventional dual-blinder PSB/OST schemes. They highlight interoperability issues concerning fast power swings and unconventional impedance trajectories, and propose revised relay settings in attempts to deal with the problems. However, the blinder-based PSB methodology suffers from being dependent on the speed of the apparent impedance just as it crosses between the blinders. It is therefore important to consider alternative methods. This paper thoroughly analyzes the characteristics of the swing center voltage (SCV) and the impacts of grid-forming (GFM) and grid-following (GFL) inverters on its local estimation. Then, an SCV-based PSB/OST scheme is proposed, where the main PSB criterion can be tuned from simple system parameters. This is made possible by a separate PSB activation function. The OST scheme uses only one setting and is motivated from the analytical analysis of the SCV with IBRs. Extensive PSCAD/EMTDC simulations verify the performance of the proposed SCV-based PSB/OST scheme and how it overcomes limitations of blinder-based schemes with GFM and GFL inverters.

Comment
10 pages, 13 figures

Closest papers

Nearest neighbours by meaning across the whole index.

Power-Swing Blocking Scheme Based on Continuous and Higher-Order Incremental Quantities for Systems with Inverter-Based Resources

eess.SY ·2026-11-05 ·Henrik Johansson, Qianli Xing, Nathaniel Taylor, Xiongfei Wang
similarity 0.86
Abstract · 9 pages, 11 figures

Conventional power-swing blocking (PSB) schemes for distance protection face new and emerging challenges as the penetration levels of inverter-based resources (IBRs) increase. Several papers highlight interoperability issues concerning faster power swings and unconventional impedance trajectories. Revised relay settings are proposed in attempts to deal with the problems. However, the blinder-based PSB methodology suffers from being dependent on the speed of the apparent impedance trajectory over the tiny region between the blinders, making it difficult to distinguish between fast swings and faults. Moreover, blinders have the inherent limitation that they cannot operate if the measured impedance is inside the blinders when the fault is cleared and immediately enters the distance zones during the first swing cycle - an issue often overlooked in the current literature. This paper proposes a novel PSB scheme based on higher-order incremental quantities (IQs) for difficult swing scenarios with IBRs and synchronous generators (SGs). PSCAD/EMTDC simulations of an SG and an implemented grid-forming (GFM) inverter validate its superior performance compared to conventional dual-blinder PSB schemes. The impacts of GFM inverters on the impedance measured by distance relays during the fault-to-swing transition and first power swing cycle are also discussed.

0.39

Advanced Reactance Method - A Novel Approach for Distance Protection in Presence of Grid-Following Inverter-Based-Resources

eess.SY ·2026-11-21 ·Jonathan Loebel, Jannik Polster, Johann Jaeger
similarity 0.64
Abstract

Renewable Energy Sources and consequently inverter-based resources (IBRs) are increasing worldwide. Grid-following (GFL) IBR control is the state-of-the-art. GFL IBRs exhibit different fault behavior compared to classical synchronous generators -- particularly in terms of Fault-Ride-Through (FRT) characteristics, which are critical for grid protection relaying. Grid protection must work securely, selectively and dependably, regardless of the feeding source. As common protection algorithms are designed for fault behavior determined by synchronous generators, their performance is expected to be compromised in the presence of GFL IBRs. Distance Protection is a widely used protection algorithm at all voltage levels. Literature shows that the FRT behavior of GFL IBRs impacts the Distance Protection relaying adversely. This paper proposes the Advanced Reactance Method, a further development of the Classical Reactance Method for Distance Protection in the presence of GFL IBRs. The key idea of the proposed method is to make the algorithm independent of the feeding source impedance. Therefore, the negative sequence voltage is taken into account along with the negative sequence current. This makes the algorithm independent of the FRT behavior of GFL IBRs, even in case of suppression of negative sequence current during unsymmetrical faults. Moreover, correct settings for the classical method in the presence of GFL IBRs are presented as a solution for relays without the advanced method. The novel algorithm is evaluated against the correctly parameterized Classical Reactance Method and the Distance Protection algorithm.

0.18

A Novel Asymmetric Distributed Voltage Regulation Scheme to Enhance the Utilization of Distributed Energy Resources

eess.SY ·2026-11-05 ·Madhura Sondharangalla, Dan Moldovan, Raja Ayyanar
published similarity 0.56
Abstract

Passive voltage regulation in distribution grids using distributed energy resources (DERs) is becoming the standard for feeder voltage management in both under-voltage and over-voltage scenarios. Their simple control, ease of implementation, and fast response make them ideal for distribution feeders with high-DER penetration. This paper proposes a novel distributed voltage control for DERs based on the voltage at the point of common coupling, inverter rating, and operating active power. The proposed control is designed to utilize feeder inverters efficiently to reduce the burden on the inverters in both under-voltage and over-voltage operations and increase the fairness in reactive power ($Q$) support in over-voltage operations. The proposed control is implemented in static and dynamic simulations of a real feeder to validate the performance. Results for the under-voltage scenario are also presented in the paper.

0.36

Local Energy Function-Based Power System Transient Stability Analysis with Grid Forming and Grid Following Inverters

eess.SY ·2026-09-06 ·Yingyi Tang, Junbo Zhao, Baosen Zhang
similarity 0.55
Abstract

The widespread deployment of inverter-based resources (IBRs) is reshaping power system dynamics by their control strategies. Grid-following (GFL) and grid-forming (GFM) inverters are expected to co-exist from now on. However, ensuring the transient stability of such systems remains a critical and underexplored challenge. In this paper, a comprehensive transient stability analysis of the mixed-GFM-GFL inverter system is conducted using a newly derived local energy function. The transient stability analysis model of the system is first derived to reveal the dynamic interactions between GFL and GFM inverters during transient responses. A local energy function is then proposed for analytical transient stability assessment. Instead of ignoring or making harsh assumptions on inverters' coupled damping effect, the proposed local energy function carefully addresses its impact on system transient stability by locally bounding the region where the system's energy dissipation property holds. Such a property fully considers the combined damping effect of GFL and GFM inverters. The derived critical energy and stability index provide a fast and quantitative transient stability assessment. Furthermore, the adverse impact of insufficient damping of GFM inverters on system transient stability is thoroughly investigated. The effectiveness of the proposed method is validated on the modified IEEE 14-bus system with mixed GFL and GFM inverters, and the numerical simulation results further demonstrate the small conservativeness of the proposed method.

0.24

On the Achievable Inertia Constant of Inverter Based Resources

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.53
Abstract · Under Review in IEEE Transactions on Power Systems

As inverter-based resources (IBRs) displace synchronous generators, the inertia they can actually contribute to the grid becomes a critical planning parameter. Unlike synchronous machines, this contribution is bounded simultaneously by the available energy reserve, the converter power rating combined with voltage ride-through (VRT) obligations, and the inertia-emulation control scheme with its activation delay. This paper derives each bound in closed form and combines them into a unified envelope $\Heff(t,λ,V_g)=\min(\HE,\HP,\HC)$, which uses parameters accessible to the system operator to quantify how much inertia a plant can provide at a given loading $λ$, grid voltage $V_g$, and time $t$ after a disturbance. The analysis shows that below a loading-dependent critical voltage, VRT reactive-current priority does not leave active-current headroom for inertial power injection; that the converter overload ratio $κ$ matters mainly during voltage dips; and that de-loading yields a linear, quantifiable inertia gain, while collocated energy storage (ESS) removes the source-coupling constraint, making grid-following (GFL) and grid-forming (GFM) plants with storage equivalent post-activation, up to the GFL activation-delay discount within short RoCoF measurement windows. Simulations on the IEEE 9-bus system confirm the framework and motivate a two-dimensional inertia capability curve $H(λ,V_{g,\min})$ as a grid-code instrument analogous to the P--Q diagram of synchronous generators.

0.28

Relative-Degree Wall Restricts Passivity-Based Stability Analysis in Inverter-Dominant Grids

eess.SY ·2026-08-30 ·Xiaoyu Peng, Zhongze Li, Xi Ru, Xinghua Chen, Feng Liu
top venue similarity 0.53
Abstract

This letter reveals a fundamental limitation of passivity-based distributed stability analysis in power systems. Under the standard formulation, passivity certification inherently imposes a relative-degree compatibility constraint that excludes many high-fidelity inverter dynamic models (e.g., those that include electromagnetic transients). Potential extensions of passivity frameworks are discussed to break this limitation.

0.43

Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

eess.SY ·2026-10-20 ·Amir H. Abolmasoumi, Hamed Mohsenian-Rad
published similarity 0.53
Abstract · Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

0.29

Frequency Measurement Practices for Inertia Assessment in Inverter Based Resources Dominated Power Systems

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.53
Abstract · Under Review in IEEE Transactions on Power Systems

Transmission system operators and protective relays compute the rate of change of frequency (RoCoF) from frequency averaged over tens to hundreds of milliseconds, as standards and grid codes specify. Any response delivered inside that window lowers the measured RoCoF, so the inferred inertia depends on the window and the responses in service. This paper defines the windowed inertia estimate and derives an exact identity the system inertia divided by one minus the fraction of the disturbance energy delivered inside the window and a closed-form prediction that applies the same estimator to the trajectory of a linear response model. Eleven IEEE 9-bus RMS runs synchronous, grid-following and grid-forming configurations, disturbance sizes and parameter sweeps are reproduced by that model, and the identity closes on the measured response powers. Fast frequency response inflates the estimate most: at 500 ms a grid-following system with 20 % less synchronous inertia reports the same value as the all-synchronous system, the grid-forming system a higher one. On a reduced Greek transmission system the 500ms estimate exceeds the inertia by 17-26%, and a scenario with 10% less synchronous inertia reports more than the all-synchronous scenario's inertia. Operators can thus compute what their measurement reports.

0.26